Mitsubishi Electric FR-F820-00077 Instruction Manual page 885

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Specifications
Pulse train
output
(FM type)
Current
For meter
output
(CA type)
Voltage
output
Operating
Operation
status
panel
(FR-DU08)
Fault record
Protective
function
Protective/
warning
function
Warning
function
Surrounding air
temperature
Surrounding air humidity
Storage temperature
Atmosphere
Altitude/vibration
Tab. 8-7:
Common specifications (2)
Available only for the standard model.
This protective function is not available in the initial status.
Temperature applicable for a short time, e.g. in transit.
For the installation at an altitude above 1,000 m up to 2,500 m, derate the rated current 3% per
500 m.
2.9 m/s² for the FR-F840-04320(185K) or higher.
Available only for the FR-F800-E series.
Not available for the FR-F800-E series.
FR-F800
Max. 2.4 kHz: one terminal (output frequency)
The monitored item can be changed using Pr. 54 "FM/CA terminal function selection".
Max. 20 mA DC: one terminal (output current)
The monitored item can be changed using Pr. 54 "FM/CA terminal function selection".
Max. 10 V DC: one terminal (output voltage)
The monitored item can be changed using Pr. 158 "AM terminal function selection".
Output frequency, output current, output voltage, frequency setting value
The monitored item can be changed using Pr. 52 "Operation panel main monitor selection".
Fault record is displayed when a fault occurs. Past 8 fault records and the conditions immediately before the
fault (output voltage/current/frequency/cumulative energization time/year/month/date/time) are stored.
Overcurrent trip during acceleration, overcurrent trip during constant speed, overcurrent trip during
deceleration or stop, Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip during
constant speed, Regenerative overvoltage trip during deceleration or stop, Inverter overload trip (electronic
thermal relay function), Motor overload trip (electronic thermal relay function), Heatsink overheat,
Instantaneous power failure , Undervoltage , Input phase loss
synchronism detection , Upper limit fault detection, Lower limit fault detection, Brake transistor alarm
detection , Output side earth (ground) fault overcurrent, Output short circuit, Output phase loss, External
thermal relay operation , PTC thermistor operation , Option fault, Communication option fault, Parameter
storage device fault, PU disconnection, Retry count excess , CPU fault, Operation panel power supply short
circuit, RS-485 terminal power supply short circuit , 24 V DC power fault, Abnormal output current detection
, Inrush current limit circuit fault , Communication fault (inverter), Ethernet communication fault
Analog input fault, USB communication fault, Safety circuit fault, Overspeed occurrence , 4 mA input fault ,
Pre-charge fault , PID signal fault , Internal circuit fault, User definition error in the PLC function
Fan alarm, Stall prevention (overcurrent), Stall prevention (overvoltage), Regenerative brake pre-alarm
Electronic thermal relay function pre-alarm, PU stop, Parameter copy, Safety stop, Maintenance timer 1 to 3 ,
USB host error, Operation panel lock , Password locked , Parameter write error, Copy operation error, 24 V
external power supply operation, Load fault warning, Emergency drive in operation , Continuous operation
during communication fault, Ethernet communication fault
-10 °C to +50 °C (non-freezing) (LD rating)
-10 °C to +40 °C (non-freezing) (SLD rating)
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95% RH or less (non-condensing),
Without circuit board coating: 90% RH or less (non-condensing)
-20 °C to +65 °C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
Maximum 1000 m above sea level , 5.9 m/s
, Stall prevention stop, Loss of
2
or less
at 10 to 55 Hz (directions of X, Y, Z axes)
Common specifications
,
,
8 - 11