(M) Monitor display and monitor output signal
Inverter operation ready signals (RY signal) and inverter running signals (RUN, RUN3 signals)
Fig. 5-95:
– When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON
(stays ON during operation.)
– When the inverter output frequency reaches Pr. 13 "Starting frequency" or higher, the Inverter
running (RUN) signals turn ON. The signal is OFF while the inverter is stopped and during DC
injection brake operation.
– The Inverter running and start command is ON (RUN3) signal is ON while the inverter is running
or the start signal is ON. (When the start command is ON, the RUN3 signal output turns ON
even while the inverter's protective function is activated or the MRS is ON.) During DC injection
brake operation as well, the output is ON, and when the inverter stops, it turns OFF.
● According to the inverter condition, the ON/OFF operation of each signal is as shown below.
Output
signal
RY
RUN
RUN3
Tab. 5-102: Output signal output
OFF during power failure or undervoltage.
Output is shutoff in conditions like a fault and when the MRS signal is ON.
OFF while power is not supplied to the main circuit power supply.
5 - 238
Power supply
STF
RH
Reset
processing
RY
RUN
RUN3
Ready and motor running signals
Start
Start
Start
signal OFF
signal ON
signal ON
(during
(during
(running)
stop)
stop)
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
OFF
ON
Pr. 13
ON
ON
ON
DC
Output shutoff
injection
brake
operation
Start
signal ON
ON
OFF
OFF
OFF
ON
ON
OFF
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
OFF
OFF
Automatic restart after
instantaneous power failure
Coasting
Start
Start
Start
signal OFF
signal ON
signal OFF
ON
OFF
OFF
ON
OFF
Parameters
I003030E
Restart-
ing
ON
ON
ON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents