Control circuit
Output signal
Terminal
symbol
A1,
B1,
C1
A2,
B2,
C2
RUN
SU
OL
IPF
FU
SE
FM
AM
CA
Tab. 2-19:
Terminal FM is provided in the FM-type inverter.
Terminal CA is provided in the CA-type inverter.
2 - 48
Terminal name
Terminal function description
1 changeover contact output that indicates that
an inverter's protective function has been
activated and the outputs are stopped.
Relay output 1 (fault
output)
Fault: discontinuity across B and C (continuity
across A and C), Normal: continuity across Band C
(discontinuity across A and C)
Relay output 2
1 changeover contact output
Switched to LOW when the inverter output
frequency is equal to or higher than the starting
Inverter running
frequency (initial value 0.5 Hz). Switched to HIGH
during stop or DC injection brake operation.
Switched to LOW when the
output frequency is within
the set frequency range
Up to frequency
±10% (initial value). Switched
to HIGH during acceleration/
deceleration and at a stop.
Switched to LOW when stall
prevention is activated by
Overload warning
the stall prevention function.
Switched to HIGH when stall
prevention is cancelled.
Switched to LOW when an
instantaneous power failure
Instantaneous power
occurs or when the
failure
undervoltage protection is
activated.
Switched to LOW when the
inverter output frequency is
equal to or higher than the
Frequency detection
preset detection frequency,
and to HIGH when it is less
than the preset detection
frequency.
Open collector
Common terminal for terminals RUN, SU, OL, IPF,
output common
FU
For meter
Outputs a selected
monitored item (such as
output frequency) among
several monitored items. The
NPN open
signal is not output during
collector output
an inverter reset.
The output signal is
proportional to the
magnitude of the
corresponding monitoring
Analog voltage
item.
output
Use Pr. 55, Pr. 56, and Pr. 866
to set full scales for the
monitored output frequency,
output current, and torque.
Analog current
(Refer to page 5-211.)
output
Output signals
Installation and wiring
Rated specification
Contact capacity
230 V AC 0.3 A
(power factor = 0.4)
30 V DC 0.3 A
Permissible load
24 V DC (maximum
27 V DC) 0.1 A
(The voltage drop is
2.8 V at maximum
while the signal is
ON.)
LOW is when the
Fault code (4 bits)
open collector output
output. (Refer to
transistor is ON
page 5-252.)
(conducted).
HIGH is when the
transistor is OFF (not
conducted).
Permissible load
Output item:
current 2 mA
Output frequency
For full scale
(initial setting)
1440 pulses/s
Maximum output
This terminal can
pulse 50k pulses/s
be used for open
collector outputs
Permissible load
by setting Pr. 291.
current 80 mA
Output signal 0 to
±10 V DC,
Permissible load
current 1 mA
(load impedance
Output item:
10 kΩ or more)
Output frequency
Resolution 8 bits
(initial setting)
Load impedance
200 Ω to 450 Ω
Output signal
0 to 20 mA DC
Refer
to
page
5-231
5-231
5-231
5-240
5-194
5-415,
5-432
5-240
5-211
5-140
5-211
5-211