Supported BACnet object
● Analog input
Object
identifier
0
1
2
Tab. 5-265: Object assignment for analog inputs
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
● Analog output
Object
identifier
0
1
Tab. 5-266: Object assignment for analog outputs
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array,
even when "Write Access Denied" is returned due to inconsistency of the writing requirements
such as the operating mode, on condition that the values are written within the setting range.
Available regardless of the operation mode, operation command source, and speed command
source.
FR-F800
Present value
Object name
access type
Terminal 1
R
Terminal 2
R
Terminal 4
R
Present value
Object name
access type
Terminal FM (CA)
C
Terminal AM
C
(N) Operation via communication and its settings
Description
Represents actual input voltage of terminal 1.
(The range varies depending on the Pr. 73 and
Pr. 267 settings.
–10 to +10 V (–100% to +100%),
–5 to +5 V (–100% to +100%) )
Represents actual input voltage (or input
current) of terminal 2.
(The range varies depending on the Pr. 73 and
Pr. 267 settings.
0 to 10 V (0% to 100%),
0 to 5 V (0% to 100%),
0 to 20 mA (0% to 100%) )
Represents actual input voltage (or input
current) of terminal 4.
(The range varies depending on the Pr. 73 and
Pr. 267 settings.
2 to 10 V (0% to 100%),
1 to 5 V (0% to 10 0%),
4 to 20 mA (0% to 100%) )
Description
Controls actual output current level of terminal
FM/CA.
Control is available when Pr. 54 "FM/CA
terminal function selection" = "85" .
(Setting range: 0 to 200%)
Controls actual output voltage level of
terminal AM.
Control is available when Pr. 158 "AM terminal
function selection" = "86" .
(Setting range: -200 to 200%)
Unit
percent (98)
percent (98)
percent (98)
Unit
percent (98)
percent (98)
5 - 511