Mitsubishi Electric FR-F820-00077 Instruction Manual page 686

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

(N) Operation via communication and its settings
● Binary Input
Object
identifier
0
1
2
3
4
5
6
7
8
9
10
11
100
101
102
103
104
105
106
107
Tab. 5-268: Object assignment for binary inputs
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
● Binary Output
Object
identifier
0
1
2
3
4
5
6
Tab. 5-269: Object assignment for binary outputs
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array,
even when "Write Access Denied" is returned due to inconsistency of the writing requirements
such as the operating mode, on condition that the values are written within the setting range.
Available regardless of the operation mode, operation command source, and speed command
source.
5 - 514
Present value
Object name
access type
Terminal STF
Terminal STR
Terminal AU
Terminal RT
Terminal RL
Terminal RM
Terminal RH
Terminal JOG
Terminal MRS
Terminal STOP
Terminal RES
Terminal CS
Terminal RUN
Terminal SU
Terminal IPF
Terminal OL
Terminal FU
Terminal ABC1
Terminal ABC2
Terminal SO
Present value
Object name
access type
Terminal RUN CMD
Terminal SU CMD
Terminal IPF CMD
Terminal OL CMD
Terminal FU CMD
Terminal ABC1 CMD
Terminal ABC2 CMD
Description (0: Inactive, 1: Active)
R
Represents actual input of terminal STF.
R
Represents actual input of terminal STR.
R
Represents actual input of terminal AU.
R
Represents actual input of terminal RT.
R
Represents actual input of terminal RL.
R
Represents actual input of terminal RM.
R
Represents actual input of terminal RH.
R
Represents actual input of terminal JOG.
R
Represents actual input of terminal MRS.
R
Represents actual input of terminal STOP.
R
Represents actual input of terminal RES.
R
Represents actual input of terminal CS.
R
Represents actual output of terminal RUN.
R
Represents actual output of terminal SU.
R
Represents actual output of terminal IPF.
R
Represents actual output of terminal OL.
R
Represents actual output of terminal FU.
R
Represents actual output of terminal ABC1.
R
Represents actual output of terminal ABC2.
R
Represents actual output of terminal SO.
Description (0: Inactive, 1: Active)
Controls actual output of terminal RUN.
C
Available when Pr. 190 = "82 or 182".
Controls actual output of terminal SU.
C
Available when Pr. 191 = "82 or 182".
Controls actual output of terminal IPF.
C
Available when Pr. 192 = "82 or 182".
Controls actual output of terminal OL.
C
Available when Pr. 193 = "82 or 182".
Controls actual output of terminal FU.
C
Available when Pr. 194 = "82 or 182".
Controls actual output of terminal ABC1.
C
Available when Pr. 195 = "82 or 182".
Controls actual output of terminal ABC2.
C
Available when Pr. 196 = "82 or 182".
Parameters

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents