Parameters
● When using the cleaning function for the purpose of periodic maintenance in such applications
that require continuous pump operation for a long time, use a time trigger. The time trigger is
enabled by setting a time period before starting the cleaning operation in Pr. 1479 "Cleaning time
trigger". The timer starts when the timer starting condition is satisfied, and the cleaning operation
is performed at a time interval set in Pr. 1479.
● Starting conditions of the timer for a time trigger
– When the start command turns ON
– When the cleaning ends
Y215
Output
frequency
Fig. 5-158:
Cleaning operation by the cleaning signal (X97 signal)
● When the X97 signal is assigned to an input terminal, the cleaning operation can be finished when
the cleaning signal (X97) is turned from ON to OFF.
● For the X97 signal input, set "97" in any of Pr. 178 to Pr. 189 to assign the function.
Pr. 1470 setting
0
Other than 0
Tab. 5-166: Finishing the cleaning operation with cleaning signal (X97)
FR-F800
STF
ON
Start command ON trigger
ON
0 Hz
Cleaning
operation
(Pr. 1470 = Once)
Starting conditions of the timer for a time trigger
X97 signal
Assignment
Optional
Not assigned
Assigned
Time trigger
ON
Pr. 1479
Pr. 1479
Normal
Cleaning
operation
operation
operation
(Pr. 1470 = Once)
Cleaning
operation
ON/OFF
Optional
Invalid
Enabled
OFF
Invalid
ON
Enabled
(A) Application parameters
Time trigger
ON
Normal
Cleaning
Normal
operation
operation
(Pr. 1470 = Once)
Cleaning end condition
After cleaning is performed for the
number of times set in Pr. 1470
After cleaning is performed for
the number of times set in
Pr. 1470
When X97 signal turns OFF
Time
I003039E
5 - 351