Mitsubishi Electric FR-F820-00077 Instruction Manual page 68

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Main circuit terminals
SLD rating (Pr. 570 "Multiple rating setting" = "0")
● 200 V class (220 V input power supply)
Terminal
Applicable
screw
inverter model
FR-F820-
size
00046(0.75K) to
M4
00105(2.2K)
00167(3.7K)
M4
00250(5.5K)
M4
00340(7.5K)
M5
00490(11K)
M5
00630(15K)
M5
00770(18.5K)
M6
00930(22K)
M8(M6)
01250(30K)
M8(M6)
01540(37K)
M8(M6)
01870(45K)
M10(M8)
02330(55K)
M10(M8)
03160(75K)
M12(M8)
03800(90K)
M12(M8)
04750(110K)
M12(M8)
Tab. 2-13:
Cable size (200 V class), SLD rating
● 400 V class (440 V input power supply )
Terminal
Applicable
screw
inverter model
FR-F840-
size
00023(0.75K) to
M4
00083(3.7K)
00126(5.5K)
M4
00170(7.5K)
M4
00250(11K)
M4
00310(15K)
M5
00380(18.5K)
M5
00470(22K)
M6
00620(30K)
M6
00770(37K)
M6
00930(45K)
M8
01160(55K)
M8
01800(75K)
M8
02160(90K)
M10
02600(110K)
M10
03250(132K)
M10(M12)
03610(160K)
M10(M12)
04320(185K)
M12(M10)
04810(220K)
M12(M10)
05470(250K)
M12(M10)
06100(280K)
M12(M10)
06830(315K)
M12(M10)
Tab. 2-14:
Cable size (400 V class), SLD rating
2 - 40
Crimping
terminal
Tighten-
ing
torque
R/L1,
R/L1,
Nm
S/L2,
U, V, W
S/L2,
T/L3
1.5
2-4
2-4
1.5
5.5-4
5.5-4
1.5
5.5-4
5.5-4
2.5
14-5
8-5
2.5
14-5
14-5
2.5
22-5
22-5
4.4
38-6
38-6
7.8
38-8
38-8
7.8
60-8
60-8
7.8
80-8
80-8
14.7
100-10 100-10
14.7
100-10 100-10
24.5
150-12 150-12
24.5
100-12 100-12
24.5
100-12 100-12 2×100
Crimping
terminal
Tighten-
ing
torque
R/L1,
R/L1,
Nm
S/L2,
U, V, W
S/L2,
T/L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
5.5-4
5.5-4
1.5
5.5-4
5.5-4
2.5
8-5
8-5
2.5
14-5
8-5
4.4
14-6
14-6
4.4
22-6
22-6
4.4
22-6
22-6
7.8
38-8
38-8
7.8
60-8
60-8
7.8
60-8
60-8
14.7
80-10
80-10
14.7
100-10 100-10
14.7
150-10 150-10
14.7
150-10 150-10
24.5
100-12 100-12 2×100
24.5
100-12 100-12 2×100
46
150-12 150-12 2×125
46
150-12 150-12 2×150
46
200-12 200-12 2×200
HIV cables, etc. (mm²)
Earthing
(ground-
U, V, W P/+, P1
ing)
T/L3
cable
2
2
2
2
3.5
3.5
3.5
3.5
5.5
5.5
5.5
5.5
14
8
14
5.5
14
14
14
8
22
22
22
14
38
38
38
14
38
38
38
22
60
60
60
22
80
80
80
22
100
100
100
38
100
100
100
38
125
125
150
38
150
150
2×100
38
2×100
2×100
60
HIV cables, etc. (mm²)
Earthing
(ground-
U, V, W P/+, P1
ing)
T/L3
cable
2
2
2
2
2
2
3.5
3.5
3.5
3.5
3.5
3.5
5.5
5.5
5.5
5.5
8
8
8
5.5
14
8
14
8
14
14
22
14
22
22
22
14
22
22
22
14
38
38
38
22
60
60
60
22
60
60
60
22
80
80
80
22
100
100
100
38
125
125
100
38
150
150
150
38
2×100
2×100
60
2×100
2×100
60
2×125
2×125
60
2×150
2×125
60
2×200
2×150
100
Installation and wiring
Cable gauge
AWG/MCM
PVC cables, etc. (mm²)
R/L1,
R/L1,
S/L2,
U, V, W
S/L2,
U, V, W
T/L3
T/L3
14
14
2.5
12
12
4
10
10
6
6
8
16
6
6
16
4
4
25
2
2
50
2
2
50
1/0
1/0
50
3/0
3/0
70
4/0
4/0
95
4/0
4/0
95
250
250
2×4/0
2×4/0
2×4/0
2×4/0
Cable gauge
AWG/MCM
PVC cables, etc. (mm²)
R/L1,
R/L1,
S/L2,
U, V, W
S/L2,
U, V, W
T/L3
T/L3
14
14
2.5
12
14
2.5
12
12
4
10
10
6
8
8
10
6
8
16
6
6
16
4
4
25
4
4
25
1
2
50
1/0
1/0
50
1/0
1/0
50
3/0
3/0
70
4/0
4/0
95
250
250
120
300
300
150
2×4/0
2×4/0
2×95
2×4/0
2×4/0
2×95
2×250
2×250
2×120
2×300
2×300
2×150
2×350
2×350
2×185
Earthing
(ground-
ing)
cable
2.5
2.5
4
4
6
6
10
16
16
16
25
16
50
25
50
25
50
25
70
35
95
50
95
50
Earthing
(ground-
ing)
cable
2.5
2.5
2.5
4
4
4
6
10
10
10
10
16
16
16
25
16
25
16
50
25
50
25
50
25
70
35
95
50
120
120
150
95
2×95
95
2×95
95
2×120
120
2×150
150
2×185
2×95

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents