Mitsubishi Electric FR-F820-00077 Instruction Manual page 256

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

(E) Environment setting parameters
GOT initial setting (RS-485 terminals) (Pr. 999 = "11, 13")
Pr.
79
332
333
334
335
336
337
340
341
414
549
Tab. 5-37:
When Pr. 414 = "1", the setting value is not changed.
● Initial setting with the GOT2000 series
– When "FREQROL 500/700/800, SENSORLESS SERVO" is selected for "Controller Type" in the GOT
setting, set Pr. 999 = "11" to configure the GOT initial setting.
– When "FREQROL 800 (Automatic Negotiation)" is selected for "Controller Type" in the GOT
setting, the GOT automatic connection can be used. When "FREQROL 800 (Automatic Negoti-
ation)" is selected for "Controller Type" in the GOT setting and the GOT automatic connection
is not used, set Pr. 999="13" to configure the GOT initial setting. (Refer to page 5-532 .)
● Initial setting with the GOT1000 series
– Set Pr. 999 = "10" to configure the GOT initial setting.
NOTES
Always perform an inverter reset after the initial setting.
For the details of connection with GOT, refer to the Instruction Manual of GOT.
5 - 84
Name
Operation mode selection
RS-485 communication speed
RS-485 communication stop bit length
RS-485 communication parity check
selection
RS-485 communication retry count
RS-485 communication check time
interval
RS-485 communication waiting time
setting
Communication startup mode selection
RS-485 communication CR/LF selection
PLC function operation selection
Protocol selection
GOT initial setting (RS-485 terminals)
Initial
Pr. 999 = "11"
Pr. 999 = "13"
value
0
0
96
192
1
10
2
1
1
9999
0 s
9999
9999
0 ms
0
1
1
1
0
0
0
Parameters
Refer to page
1
5-119
1152
0
1
5-467
9999
9999
0 ms
1
5-128
1
5-467
5-439
2
0
5-488