Parameters
I/O signals
● When the PID control valid (X14) signal is assigned to the input terminal by setting Pr. 178 to Pr. 189
(input terminal function selection), the multi-pump function is enabled only at turn-ON of the
X14 signal.
● Use Pr. 190 to Pr. 196 (output terminal function selection) or plug-in option (FR-A8AR) to assign
functions of motor control signal to Pr. 320 to Pr. 322 (RA output selection). (Only positive logic is
available.)
Output signal
SLEEP
RO1
RO2
RO3
RO4
RIO1
RIO2
RIO3
RIO4
Tab. 5-194: I/O signals
The value cannot be set in Pr. 320 to Pr. 322.
Negative logic cannot be set.
FR-F800
Pr.190 to Pr.196 and Pr.320 to Pr.322 settings
Positive logic
Negative logic
70
71
72
73
74
75
76
77
78
Function
PID output interruption
170
Commercial power supply side motor 1
connection RO1
Commercial power supply side motor 2
connection RO2
Commercial power supply side motor 3
connection RO3
Commercial power supply side motor 4
connection RO4
Inverter side motor 1 connection RIO1
Inverter side motor 2 connection RIO2
Inverter side motor 3 connection RIO3
Inverter side motor 4 connection RIO4
(A) Application parameters
5 - 397