Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Parameters
Be careful of the capacity of the sequence output terminals.
The applied terminals differ by the settings of Pr. 190 to Pr. 196 (output terminal function selection).
Output terminal capacity
Open collector output of inverter (RUN, SU, IPF, OL, FU)
Inverter relay output (A1-C1, B1-C1, A2-B2, B2-C2)
Relay output option (FR-A8AR)
When connecting a DC power supply, insert a protective diode.
When connecting an AC power supply, use the relay output option (FR-A8AR) and use contact
outputs.
The applied terminals differ by the settings of Pr. 180 to Pr. 189 (input terminal function selection).
To use the signal, assign the function to the output terminal Pr. 190 to Pr. 195 (output terminal
function selection) of the converter unit. It is recommended, that the wiring of the ALM signal is
always proof against wire breaks. High signal = no fault.
NOTES
Use the electronic bypass function in External operation mode. In addition, the wiring terminals
R1/L11 and S1/L21 must be connected to a separate power source that does go through MC1. Be
sure to connect using a separate power supply.
Be sure to provide a mechanical interlock for MC2 and MC3.
● Operation of magnetic contactor (MC1, MC2, MC3)
Magnetic
contactor
MC1
MC2
MC3
Tab. 5-157: Operations of magnetic contactors
FR-F800
Installation location
Between power supply and
inverter input side
Between power supply and
motor
Between inverter output side
and motor
Output terminal permissible load
During commercial
During inverter
power supply
operation
operation
Shorted
Shorted
Shorted
Open
Shorted
(A) Application parameters
24 V DC 0.1 A
230 V AC 0.3 A
30 V DC 0.3 A
Operation
During inverter fault
Open
(short by reset)
Open
(Selected by Pr. 138.
Open
Always open when the
external thermal relay is
operating.)
Open
5 - 335