Parameters
Output up-to-frequency sensitivity (SU signal, Pr. 41)
● Up to frequency (SU) is output when the output frequency reaches the set frequency.
● The Pr. 41 value can be adjusted within the range ±1% to ±100% considering the set frequency
as 100%.
● This parameter can be used to check that the set frequency has been reached, and provide signals
such as the operation start signal for related equipment.
SU
FR-F800
Set frequency
Adjustment
range Pr. 41
OFF
OFF
ON
(M) Monitor display and monitor output signal
Fig. 5-97:
Output of the SU signal
Time
I002626E
5 - 241