Mitsubishi Electric FR-F820-00077 Instruction Manual page 486

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

(C) Motor constant parameters
Changing the motor constant (if setting the Pr. 92 and Pr. 93 motor constants in units of [Ω])
● Set Pr. 71 as shown below.
Applicable motor
Standard motor
Constant-torque motor
● Set a given value as the motor constant parameter.
lq
=
Iq = torque current, I
First
motor Pr.
82
90
91
92
93
94
859
298
Tab. 5-143: Parameter setting ranges
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
For the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
NOTES
If "star connection" or "delta connection" is incorrectly selected in Pr. 71, Advanced magnetic flux
vector control is not performed normally.
If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi motors (SF-PR, SF-
JR, SF-HR, SF-JRCA, SF-HRCA and so on) are used.
5 - 314
2
2
I 100
I 0
= rated current, I
100
Second
Name
motor Pr.
Motor excitation
455
current
(No-load current)
458
Motor constant (r1)
459
Motor constant (r2)
460
Motor constant (×1)
461
Motor constant (×2)
462
Motor constant (×m)
Torque current/Rated
860
PM motor current
560
Frequency search gain
Pr. 71 setting
Star connection motor
5
15
= no load current
0
Setting range
0 to 500 A, 9999
0 to 3600 A, 9999
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
0 to 50 Ω, 9999
0 to 3600 mΩ, 9999
0 to 50 Ω, 9999
0 to 3600 mΩ, 9999
0 to 500 Ω, 9999
0 to 100 Ω, 9999
0 to 500 A, 9999
0 to 3600 A, 9999
0 to 32767, 9999
Parameters
Delta connection motor
6
16
Setting increments Initial value
0.01 A
0.1 A
0.001 Ω
0.01 mΩ
0.001 Ω
0.01 mΩ
0.001 Ω
9999
0.01 mΩ
0.001 Ω
0.01 mΩ
0.01 Ω
0.01 A
0.1 A
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents