Ethernet communication (FR-F800-E)
● When Pr. 544 = "18 or 28" (compatible with the octuple setting of CC-Link Ver.2)
– Remote I/O (32 points (128 points occupied))
Same as when Pr. 544 = 0 (refer to page 5-613).
– Remote register
Description
Address
Upper 8 bits
RWwn
Monitor code 2
RWwn+1
Set frequency (0.01 Hz increments)
Link parameter
RWwn+2
extended setting
RWwn+3
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
RWwn+8
Faults history No.
RWwn+9
PID set point (0.01% increments)
RWwn+A
PID measured value (0.01% increments)
RWwn+B
PID deviation (0.01% increments)
RWrn+C
RWrn+D
RWrn+E
RWrn+F
Link parameter
RWwn+10
extended setting
RWwn+11
Link parameter
RWwn+12
extended setting
RWwn+13
Link parameter
RWwn+14
extended setting
RWwn+15
Link parameter
RWwn+16
extended setting
RWwn+17
Link parameter
RWwn+18
extended setting
RWwn+19
RWwn+1A
to
RWwn+1F
Tab. 5-341:
Remote registers (write)
Valid when Pr. 128 ="50, 51, 60, or 61".
"n" indicates a value determined by the station number setting.
5 - 616
Refer to
Lower 8 bits
Monitor code 1
Instruction code
Write data
H00
H00 (Free)
H00 (Free)
H00 (Free)
H00 (Free)
Instruction code
Write data
Instruction code
Write data
Instruction code
Write data
Instruction code
Write data
Instruction code
Write data
H00 (Free)
Address
page
Upper 8 bits
5-619
RWrn
5-619
RWrn+1
RWrn+2
5-619
RWrn+3
5-619
RWrn+4
5-619
RWrn+5
5-619
RWrn+6
5-619
RWrn+7
5-619
RWrn+8
Faults history No.
5-619
RWrn+9
5-619
RWrn+A
5-619
RWrn+B
5-619
RWrn+C
RWrn+D
RWrn+E
RWrn+F
RWrn+10
RWrn+11
5-619
RWrn+12
5-619
RWrn+13
5-619
RWrn+14
RWrn+15
5-619
RWrn+16
5-619
RWrn+17
5-619
RWrn+18
RWrn+19
5-619
RWrn+1A to
5-619
RWrn+1F
5-619
Tab. 5-342:
5-619
Description
Lower 8 bits
First monitor value
Second monitor value
Reply code 2
Reply code 1
Read data
Third monitor value
Fourth monitor value
Fifth monitor value
Sixth monitor value
Fault data
Fault record (output frequency)
Fault record (output current)
Fault record (output voltage)
Fault record (energization time)
H00 (Free)
Reply code
Read data
Reply code
Read data
Reply code
Read data
Reply code
Read data
Reply code
Read data
H00 (Free)
Remote registers (read)
Parameters
Refer to
page
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620