Parameters
● Binary value
Object
identifier
0
11
98
99
200
300
301
302
303
304
305
306
307
308
309
400
401
402
Tab. 5-270: Object assignment for binary values
R: Read only,
W: Read/Write (Commandable values not supported),
C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array,
even when "Write Access Denied" is returned due to inconsistency of the writing requirements
such as the operating mode, on condition that the values are written within the setting range.
The following signals cannot be controlled by the network: Jog operation, selection of automatic
restart after instantaneous power failure, start self-holding, and reset. Therefore control input
instruction JOG, STOP, RES, and CS are invalid in the initial status. To use the control input
instruction JOG, STOP, RES, and CS, change the signals with Pr.185, Pr.186, Pr.188, Pr.189 (input
terminal function selection). (Refer to page 5-285.) (Reset is available with ReinitializeDevice.)
If communication operation command source is other than NET, the setting value can be written,
but not to be applied.
FR-F800
Present value
Object name
access type
Inverter running
Inverter operation
ready
Alarm output
Fault output
Inverter running
reverse
Control input
instruction AU
Control input
instruction RT
Control input
instruction RL
Control input
instruction RM
Control input
instruction RH
Control input
instruction JOG
Control input
instruction MRS
Control input
instruction STOP
Control input
instruction RES
Control input
instruction CS
Run/Stop
Forward/Reverse
Fault reset
(N) Operation via communication and its settings
Description
R
Represents inverter running (RUN signal) status.
R
Represents inverter operation ready (RY signal) status.
R
Represents alarm output (LF signal) status.
R
Represents fault output (ALM signal) status.
R
Represents inverter reverse running status.
Controls the function assigned to terminal AU.
C
Setting 1 of this object turns ON the signal assigned to Pr. 184.
Controls the function assigned to terminal RT.
C
Setting 1 of this object turns ON the signal assigned to Pr. 183.
Controls the function assigned to terminal RL.
C
Setting 1 of this object turns ON the signal assigned to Pr. 180.
Controls the function assigned to terminal RM.
C
Setting 1 of this object turns ON the signal assigned to Pr. 181.
Controls the function assigned to terminal RH.
C
Setting 1 of this object turns ON the signal assigned to Pr. 182.
Controls the function assigned to terminal JOG.
C
Setting 1 of this object turns ON the signal assigned to Pr. 185.
Controls the function assigned to terminal MRS.
C
Setting 1 of this object turns ON the signal assigned to Pr. 187.
Controls the function assigned to terminal STOP.
C
Setting 1 of this object turns ON the signal assigned to Pr. 188.
Controls the function assigned to terminal RES.
C
Setting 1 of this object turns ON the signal assigned to Pr. 189.
Controls the function assigned to terminal CS.
C
Setting 1 of this object turns ON the signal assigned to Pr. 186.
Controls start/stop command. Start command is written after
Speed scale is applied.
C
1: Start
0: Stop
Controls forward/reverse rotation.
C
1: Reverse rotation
0: Forward rotation
Clears fault output status. (Release of an inverter fault without
C
inverter reset is available.)
5 - 515