Tab. 5-126: Input terminal function assignment (2)
When Pr. 59 "Remote function selection" ≠ "0", functions of the RL, RM, and RH signals will be
changed as in the table.
OH signal will operate with the relay contact "open".
Available when the plug-in option is connected. For details, refer to the Instruction Manual of the
option.
The setting is available only for standard models.
NOTES
Same function can be assigned to two or more terminals. In this case, the logic of terminal input is
OR.
Priority of the speed command is JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
When the (X10) signal is not set up, Pr. 79 "Operation mode selection" = "7", and PU operation
external interlock (X12) signal is Inverter run enable signal.
Same signal is used to assign multi-speed (7 speed) and remote setting. Setting cannot be per-
formed individually.
When the terminal assignment is changed using Pr. 178 to Pr. 189 (input terminal function selec-
tion), the terminal name will be different, which may result in an error of wiring, or affect other
functions. Set parameters after confirming the function of each terminal.
FR-F800
Signal
Function
name
PU/NET operation switchover
X65
(PU operation with X65-ON)
External/NET operation switchover
X66
(NET operation with X66-ON)
Command source switchover
X67
(Command by Pr. 338, Pr. 339 enabled with X67-ON)
X70
DC feeding operation permission
X71
DC feeding cancel
X72
PID P control switchover
X73
Second PID P control switchover
X77
Pre-charge end command
X78
Second pre-charge end command
X79
Second PID forward/reverse action switchover
X80
Second PID control valid terminal
PGT
PID gain tuning start/forced end
X84
Emergency drive execution command
Control signal input for main circuit power supply
X94
MC
X95
Converter unit fault input
X96
Converter unit fault input (E.OHT, E.CPU) input
X97
Cleaning valid
X98
Cleaning trigger
No function
(T) Multi-Function Input Terminal Parameters
Related parameter
Pr. 79, Pr. 340
Pr. 79, Pr. 340
Pr. 338, Pr. 339
Pr. 30
Pr. 30
Pr. 127 to Pr. 134,
Pr. 575 to Pr. 577
Pr. 127 to Pr. 134,
Pr. 575 to Pr. 577
Pr. 760 to Pr. 764
Pr. 765 to Pr. 769
Pr. 753 to Pr. 758
Pr. 753 to Pr. 758
Pr. 1211 to Pr. 1219
Pr. 514, Pr. 515, Pr. 523, Pr. 524,
Pr. 1013
Pr. 30, Pr. 137, Pr. 248, Pr. 254
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
Pr. 1469 to Pr. 1479
Refer to
page
5-119
5-119
5-130
5-552
5-552
5-353
5-353
5-385
5-385
5-353
5-353
5-373
5-167
5-342
5-333
5-348
5 - 287