(M) Monitor display and monitor output signal
Setting
Positive
logic
71
72
73
74
75
76
77
78
79
80
82
85
86
87
88
89
90
91
92
93
Tab. 5-101: Output terminal function assignment (3)
5 - 234
Signal
Function
Negative
name
logic
Commercial power
171
RO1
supply side motor 1
connection
Commercial power
172
RO2
supply side motor 2
connection RO2
Commercial power
173
RO3
supply side motor 3
connection RO3
Commercial power
174
RO4
supply side motor 4
connection
Inverter side motor 1
175
RIO1
connection RIO1
Inverter side motor 2
176
RIO2
connection RIO2
Inverter side motor 3
177
RIO3
connection RIO3
Inverter side motor 4
178
RIO4
connection RIO4
Pulse train output of
179
Y79
output power
Safety monitor output
180
SAFE
(SAFE) signal
182
Y82
BACnet binary output
185
Y85
DC current feeding
Control circuit capacitor
life
186
Y86
(for Pr. 313 to Pr. 322)
Main circuit capacitor life
187
Y87
(for Pr. 313 to Pr. 322)
Cooling fan life
188
Y88
(for Pr. 313 to Pr. 322)
Inrush current limit circuit
life
189
Y89
(for Pr. 313 to Pr. 322)
190
Y90
Life alarm
Fault output 3(power-OFF
191
Y91
signal)
Energy saving average
192
Y92
value updated timing
Current average monitor
193
Y93
signal
Operation
Output depending on the motor drive
conditions when the multi-pump
function is used.
Output in pulses every time the
accumulated output power of the
inverter reaches the Pr. 799 setting.
The SAFE signal is output when the safety
stop function is activated and the
internal safety circuit status is normal.
Enables output from the Binary Output
object for BACnet communication.
Output when there is a power failure or
undervoltage for the AC current.
Output when the control circuit capacitor
approaches the end of its life.
Output when the main circuit capacitor
approaches the end of its life.
Output when the cooling fan approaches
the end of its life.
Output when the inrush current limit
circuit approaches the end of its life.
Output when any of the control circuit
capacitor, main circuit capacitor and
inrush current limit circuit or the cooling
fan approaches the end of its life.
Output when an error occurs due to an
inverter circuit fault or connection fault.
Switches between ON and OFF each time
the average power saving is updated
when using the power saving monitor.
This cannot be set in Pr. 195 or Pr. 196,Pr.
320 to Pr. 322 (relay output terminal).
Outputs the average current and
maintenance timer value as a pulse.
This cannot be set in Pr. 195 or Pr. 196,
Pr. 320 to Pr. 322 (relay output terminal).
Parameters
Related
Refer to
parameter
page
Pr. 575 to
5-392
Pr. 591
Pr. 799
5-253
2-65
Pr. 549
5-506
Pr. 30
5-552
Pr. 255 to
5-91
Pr. 259
5-240
Pr. 52, Pr. 54,
Pr. 158,
5-60
Pr. 891 to
Pr. 899
Pr. 555 to
5-97
Pr. 557