Mitsubishi Electric FR-F820-00077 Instruction Manual page 363

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Parameters
Read value of Pr. 1480
Tens place
8
Tab. 5-84:
● While measuring automatically, the During load characteristics measurement signal (Y213) is
output. For the Y213 signal, assign the function by setting "213 (positive logic)" or "313 (negative
logic)" in any of Pr. 190 to Pr. 196 (output terminal function selection).
● Setting "8888" in Pr. 1481 to Pr. 1485 enables fine adjustment of load characteristics. When setting
Pr. 1481 to Pr. 1485 = "8888" during operation, the load status at that point is set in the parameter.
(Only when the set frequency is within ±2 Hz of the frequency of the measurement point, and SU
signal is in the ON state)
Frequency [Hz]
STF = ON
Pr. 1480 = 1
Measurement start
Fig. 5-72:
NOTES
Even if the load measurement is not properly completed, the load characteristics fault is detected
based on the load characteristics found by the already-completed portion of the measurement.
During the load characteristics measurement, the load characteristics fault detection is not per-
formed.
During the load characteristics measurement, linear acceleration/deceleration is performed even
if the S-pattern acceleration/deceleration is set.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
FR-F800
Status
Ones place
5
During measurement from Point 4 to Point 5
0
Normal completion
Termination of measurement by an activation of a protective function, inverter reset,
1 to 5
turning ON of MRS signal, turning OFF of the start command, or timeout. (The value in
the ones place represents the above-mentioned measurement point.)
Display of the status of the measurement (Pr. 1480)
f5 (Pr. 1486)
f4
f3
Load reference 2 recorded
f2
Load reference 1
recorded
f1 (Pr. 1487)
Pr. 1492
Read value of
1
Pr. 1480
STF
Y213
ON
SU signal
SU signal
Example of starting measurement from the stop state
Load reference 4 recorded
Load reference 3 recorded
Pr. 41
Pr. 41
Pr. 41
Pr. 1492
Pr. 1492
Pr. 1492
2
3
ON
ON
ON
ON
(H) Protective function parameter
Load reference 5 recorded
Pr. 41
Pr. 41
Pr. 1492
4
5
0
ON
ON
ON
Operation at the
set frequency
Time
I003027E
5 - 191

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents