Mitsubishi Electric FR-F820-00077 Instruction Manual page 787

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Parameters
● When Pr. 544 = "14 or 24" (compatible with the quadruple setting of CC-Link Ver.2)
– Remote I/O (32 points (64 points occupied))
Same as when Pr. 544 = 0 (refer to page 5-613).
– Remote register
Description
Address
Upper 8 bits
RWwn
Monitor code 2
RWwn+1
Set frequency (0.01 Hz increments)
Link parameter
RWwn+2
extended setting
RWwn+3
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
RWwn+8
Faults history No.
RWwn+9
PID set point (0.01% increments)
RWwn+A
PID measured value (0.01% increments)
RWwn+B
PID deviation (0.01% increments)
RWwn+C
RWwn+D
RWwn+E
RWwn+F
Tab. 5-339:
Remote registers (write)
Valid when Pr. 128 = "50, 51, 60, or 61".
"n" indicates a value determined by the station number setting.
FR-F800
Refer to
Lower 8 bits
Monitor code 1
Instruction code
Write data
H00
H00 (Free)
H00 (Free)
H00 (Free)
H00 (Free)
Address
page
Upper 8 bits
5-619
RWrn
5-619
RWrn+1
5-619
RWrn+2
RWrn+3
5-619
5-619
RWrn+4
5-619
RWrn+5
5-619
RWrn+6
5-619
RWrn+7
5-619
RWrn+8
Faults history No.
5-619
RWrn+9
5-619
RWrn+A
5-619
RWrn+B
RWrn+C
RWrn+D
RWrn+E
RWrn+F
Tab. 5-340:
Ethernet communication (FR-F800-E)
Description
Lower 8 bits
First monitor value
Second monitor value
Reply code 2
Reply code 1
Read data
Third monitor value
Fourth monitor value
Fifth monitor value
Sixth monitor value
Fault data
Fault record (output frequency)
Fault record (output current)
Fault record (output voltage)
Fault record (energization time)
H00 (Free)
Remote registers (read)
Refer to
page
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5-620
5 - 615