(A) Application parameters
● The following shows the relationship between the input values of the analog input terminals and
set point, measured value and deviation. (Calibration parameter initial values)
Input
terminal
Terminal
2
Terminal
1
Terminal
4
Tab. 5-170: Relationship between the signals
Can be changed by Pr. 73 and Pr. 267 and the voltage/current input switch. (Refer to page 5-255.)
NOTE
Always perform calibration after changing the voltage/input specification with Pr. 73, Pr. 267, and
the voltage/current input selection switch.
Multistage set point input (Pr. 1460 to Pr. 1466)
● The set point can be selected by combining the ON/OFF status of the PDI1 to PDI3 signals. Up to
eight set points can be selected. Use Pr. 1460 "PID multistage set point 1" to Pr. 1466 "PID
multistage set point 7" to set the target values for selection.
● When "9999" is set in the selected multistage set point parameter, PID control is performed
according to the Pr. 128, Pr. 609, and Pr. 133 settings.
Selected set point
Multistage set point 1
Multistage set point 2
Multistage set point 3
Multistage set point 4
Multistage set point 5
Multistage set point 6
Multistage set point 7
Tab. 5-171: Multistage set point
When functions are not assigned to the input terminals, the signals are treated as OFF.
5 - 362
Inspect
specification
Set point
0 V = 0%
0 to 5 V
5 V = 100%
0 V = 0%
0 to 10 V
10 V = 100%
0 mA = 0%
0 to 20 mA
20 mA = 100%
–5 V to 0 V = 0%
0 to ±5 V
5 V = +100%
–10 V to 0 V = 0%
0 to ±10 V
10 V = +100%
0 V to 1 V = 0%
0 to 5 V
5 V = 100%
0 V to 2 V = 0%
0 to 10 V
10 V = 100%
0 to 4 mA = 0%
0 to 20 mA
20 mA = 100%
PDI1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Relationship with analog input
Result
Deviation
0 V = 0%
0 V = 0%
5 V = 100%
5 V = 100%
0 V = 0%
0 V = 0%
10 V = 100%
10 V = 100%
0 mA = 0%
0 V = 0%
20 mA = 100%
20 mA = 100%
–5 V = –100%
–5 V to 0 V = 0%
0 V = 0%
5 V = +100%
5 V = +100%
–10 V = –100%
–10 V to 0 V = 0%
0 V = 0%
10 V = +100%
10 V = +100%
0 V = –20%
0 V to 1 V = 0%
1 V = 0%
5 V = 100%
5 V = 100%
0 V = –20%
0 V to 2 V = 0%
1 V = 0%
10 V = 100%
10 V = 100%
0 V = –20%
0 to 4 mA = 0%
4 mA = 0%
20 mA = 100%
20 mA = 100%
PDI2
PDI3
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
Parameters
Calibration parameter
Pr. 125, C2 to C4
When Pr. 128 = "10",
Pr. 125, C2 to C4.
When Pr. 128 ≥ "1000",
C12 to C15.
Pr. 126, C5 to C7
Parameter for setting
As set in the Pr. 128 and Pr. 609 PID
settings.
As set Pr.1 33 when Pr. 133 ≠ "9999".
Pr. 1460
Pr. 1461
Pr. 1462
Pr. 1463
Pr. 1464
Pr. 1465
Pr. 1466