Mitsubishi Electric FR-F820-00077 Instruction Manual page 799

Fr-f800 series
Hide thumbs Also See for FR-F820-00077:
Table of Contents

Advertisement

Parameters
Programming example for reading the inverter status
The following program turns ON the signal Y00 of the output unit when the station 1 inverter starts
running.
SM1536
SD1536.0
SD1540.0
(0)
M0
X1002
(4)
(7)
Station 1
Fig. 5-290:
Programming example 1
These signals are initial values. Output signals can be changed using Pr. 190 to Pr. 196, Pr. 313 to
Pr. 315 (output terminal function selection).
FR-F800
X
1
0
0
Remote input
b15
RXF
to
RX0
0
to
RX1F
RX10
Inverter status
b0: During forward rotation
b1: Reverse rotation
b2: Running (RUN)
b3: Up to frequency (SU)
b4: Overload alarm (OL)
b5: Instantaneous power failure (IPF)
b6: Frequency detection (FU)
b7: Fault (ABC1)
b8: — (ABC2)
b16: — (DO0)
b17: — (DO1)
b18: — (DO2)
M0
Y30
END
F
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
0
0
0
0
0
0
0
[Inverter status]
Ethernet communication (FR-F800-E)
Check the data link status of the station 1.
Turn ON the signal Y00 of the output unit.
X
1
0
0
0
0
0
0
0
0
0
0
I003128E, I003129E
5 - 627