6.5 Alarm Detection
Digital Operator Display
Load is too heavy
Acceleration and deceleration times are set too
short.
The load is locked up.
Parameter settings are inappropriate.
The motor brake engaged.
Digital Operator Display
Cause
"Drive Enable" is set to a multi-function
contact input (H1-oo = 6A) and that signal
was switched off.
Digital Operator Display
Cause
The watchdog timer expired while waiting for
data from the controller.
Digital Operator Display
Cause
Sequence error
Digital Operator Display
Cause
An external fault was received from the PLC
with F6-03 = 3 (causing the drive to continue
running when an external fault occurs).
There is a problem with the PLC program.
Digital Operator Display
284
Reduce the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Check the machine.
Check the settings of parameters F1-10 and F1-11.
Ensure the brake releases properly.
dnE
Drive Disabled
Check the operation sequence.
E5
MECHATROLINK Watchdog Timer Error
Issue a DISCONNECT or ALM_CLR command, followed by a CONNECT or
SYNC_SET command and move to phase 3.
Forward/Reverse Run Command Input Error
EF
Both forward run and reverse run closed simultaneously for over 0.5 s.
Check the forward and reverse command sequence and correct the problem.
Note: Motor ramps to stop when minor fault EF is detected.
Option Card External Fault
EF0
An external fault condition is present.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Check the PLC program and correct problems.
External fault (input terminal S1)
EF1
External fault at multi-function input terminal S1.
External fault (input terminal S2)
EF2
External fault at multi-function input terminal S2.
External fault (input terminal S3)
EF3
External fault at multi-function input terminal S3.
External fault (input terminal S4)
EF4
External fault at multi-function input terminal S4.
External fault (input terminal S5)
EF5
External fault at multi-function input terminal S5.
External fault (input terminal S6)
EF6
External fault at multi-function input terminal S6.
External fault (input terminal S7)
EF7
External fault at multi-function input terminal S7.
Minor Fault Name
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
YES
Minor Fault
(H2-oo = 10)
YES
Minor Fault
(H2-oo = 10)
YES
Minor Fault
(H2-oo = 10)
YES
Minor Fault
(H2-oo = 10)
YES