5.5 E: Motor Parameters
Setting the V/f Pattern
Choose the V/f pattern that meets the application demands from the table below. Set the correct value to E1-03. The V/f
parameters E1-04 to E1-13 can only be monitored, not changed.
Note:
1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Parameter E1-03 is not reset when the drive is initialized.
Setting
0
1
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Heavy Duty 2
5
50 Hz, Heavy Duty 1
6
60 Hz, Heavy Duty 1
7
60 Hz, Heavy Duty 2
8
50 Hz, mid starting torque
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
The following tables show details on predefined V/f patterns.
The following graphs are for 200 V class drives; double the values for 400 V class drives.
Predefined V/f Patterns for 0.1 to 3.7 kW Drives
Setting = 0
50 Hz
200
16
12
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
200
35
8
0
1.3
25
50
Frequency (Hz)
170
Table 5.16 Predefined V/f Patterns
Specification
50 Hz
60 Hz
(default setting)
Table 5.17 Constant Torque Characteristics, Settings 0 to 3
Setting = 1
200
16
12
0
1.5 3
Frequency (Hz)
Table 5.18 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
200
50
9
0
1.3
25
Frequency (Hz)
Characteristic
Constant torque
Derated torque
High starting torque
Constant output
60 Hz
Setting = 2
(default)
200
16
12
60
0
1.5 3
50 Hz
Setting = 6
200
35
8
50
0
1.5
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Application
For general purpose applications. Torque remains
constant regardless of changes to speed.
For fans, pumps, and other applications that require
torque derating relative to the load.
Select high starting torque when:
• Wiring between the drive and motor exceeds
150 m
• A large amount of starting torque is required
• An AC reactor is installed
When operating at greater than 60 Hz the output
voltage will be constant.
60 Hz
Setting = 3
50
60
Frequency (Hz)
60 Hz
Setting = 7
30
60
Frequency (Hz)
72 Hz
200
16
12
0
1.5 3
60
72
Frequency (Hz)
60 Hz
200
50
9
0
1.5
30
60
Frequency (Hz)