YASKAWA CIMR-VU BA0001 Technical Manual page 467

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

Drive Model
2A0040
2A0056
2A0069
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
4A0018
4A0023
4A0031
4A0038
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your dealer or Yaskawa for instructions.
n
CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
Figure D.2 Example of DC Power Supply Input (Two Drives Connected in Series)
Note:
1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.
Refer to on page 50
3. The recommended fuses and fuse holders are made by Fuji Electric.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Model
FWH-200B
FWH-200B
FWH-200B
Three-Phase 400 V Class
FWH-40B
FWH-40B
FWH-50B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
FWH-80B
FWH-100B
FWH-125B
FWH-200B
DC power supply
(converter)
Fuse
+
_
Fuse
for an AC power supply.
Fuse Type
Manufacturer: Bussmann
Fuse Ampere Rating (A)
U/ T1
+1
V/ T2
M
_
W/ T3
Drive
U/ T1
+1
M
V/ T2
_
W/ T3
Drive
D.2 European Standards
200
200
200
40
40
50
70
70
90
90
80
100
125
200
D
467