YASKAWA CIMR-VU BA0001 Technical Manual page 382

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

B.2 Parameter Table
H3-oo
Setting
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used/Through Mode
10
FWD Torque Limit
11
REV Torque Limit
12
Regenerative Torque Limit
15
FWD/REV Torque Limit
16
Differential PID Feedback
30/31
DWEZ Analog Input 1/2
41
Output Voltage Gain
<1>
<1> Parameter available in drive software versions PRG: 1016 and later.
No.
Name
Multi-Function Analog
H4-01
Output Terminal AM
H4-02
Multi-Function Analog
<2>
Output Terminal AM Gain
H4-03
Multi-Function Analog
<2>
Output Terminal AM Bias
The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
H5-01
Drive Node Address
<3>
Communication Speed
H5-02
Selection
Communication Parity
H5-03
Selection
382
H3 Multi-Function Analog Input Settings
Function
10 V = 100%
10 V = 100.00%
Motor rated torque
Motor rated torque
Motor rated torque
Motor rated torque
10 V = 100%
Depending on function.
10 V = 100%
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
Uo-oo. For example, enter "103" for U1-03.
When using this terminal in through mode or when not using
it at all, set "000" or "031".
Sets terminal AM output gain.
Maximum output voltage is 10 V.
Sets terminal AM output bias.
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.
Selects the baud rate for MEMOBUS/Modbus terminals R+,
R-, S+ and S-. Cycle power for the setting to take effect.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
Selects the communication parity for MEMOBUS/Modbus
terminals R+, R-, S+ and S-. Cycle power for the setting to
take effect.
0: No parity
1: Even parity
2: Odd parity
Maximum Input Level Possible
Description
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Control
Mode
V/
f
O
O
O
O
O
O
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
000 to 999
102
A A A
<1>
-999.9 to
100.0
S
S
S
999.9
%
-999.9 to
0.0% A A A
999.9
0 to 20 H
1F
A A A
0 to 8
3
A A A
0 to 2
0
A A A
Pg.
O
P
L
M
V
O
O
208
O
O
208
O
O
209
O
209
O
209
O
209
O
209
O
O
209
O
O
209
209
Addr.
Pg.
Hex
41D
210
41E
210
41F
210
425
439
426
439
427
439