YASKAWA CIMR-VU BA0001 Technical Manual page 471

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

Single-Phase 200 V Class
A – Ground the cable shield
B – Enclosure panel
C – Metal plate
D – Grounding surface (remove any
paint or sealant)
E – Drive
Figure D.6 EMC Filter and Drive Installation for CE Compliance (Single-Phase 200 V Class)
n
EMC Filters
The drive should be installed with the EMC filters listed below in order to comply with the EN 61800-3:2004/A1:2012, category
C1 requirements.
Drive
Model
Type
BA0001
FS23638-10-07
BA0002
FS23638-10-07
BA0003
FS23638-10-07
BA0006
FS23638-20-07
BA0010
FS23638-20-07
BA0012
FS23638-30-07
BA0018
FS23638-40-07
2A0001
FS23637-8-07
2A0002
FS23637-8-07
2A0004
FS23637-8-07
2A0006
FS23637-8-07
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
N
L1
PE
PE
E
L1
N
J
R/L1 S/L2 T/L3
I
Table D.5 EN 61800-3:2004/A1:2012 Category C1 Filters
Filter Data (Manufacturer: Schaffner)
Rated
Weight
Current
(lb)
[W x L x H] (in)
(A)
200 V Class Single-Phase
10
0.97
10
0.97
10
0.97
20
1.65
20
1.65
30
2.42
40
2.87
200 V Three-Phase
7.3
0.88
7.3
0.88
7.3
0.88
7.3
0.88
B
C
D
E
U/T1 V/T2 W/T3
D
H
F
A
G
F – Motor cable (braided shield cable,
max. 20 m)
G – Motor
H – Cable clamp
I – Wiring distance as short as
possible
J – EMC noise filter
Mounting
Dimensions
Dimensions
[Y x X] (in)
2.8 x 6.7 x 1.8
2.0 x 6.1
2.8 x 6.7 x 1.8
2.0 x 6.1
2.8 x 6.7 x 1.8
2.0 x 6.1
4.4 x 6.7 x 2.0
3.6 x 6.1
4.4 x 6.7 x 2.0
3.6 x 6.1
5.7 x 6.9 x 2.0
4.7 x 6.3
6.9 x 6.9 x 2.0
5.9 x 6.3
2.8 x 6.7 x 1.6
2.0 x 6.1
2.8 x 6.7 x 1.6
2.0 x 6.1
2.8 x 6.7 x 1.6
2.0 x 6.1
2.8 x 6.7 x 1.6
2.0 x 6.1
D.2 European Standards
Drive
Filter
Mounting
Mounting
Screw A
Screw
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
M4
M5
471
D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents