Setting
Status
B
Closed
17
Open
18
Closed
19
Open
Setting C: Frequency Reference Loss
An output set for this function will be closed if frequency reference loss is detected.
Loss Detection Selection on page 227
Setting D: Dynamic Braking Resistor Overheat
An output programmed for this function will close when the dynamic braking resistor (DB) overheats or the braking transistor
is in a fault condition.
Setting E: Fault
The Fault configured digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and CPF01).
Setting F: Not Used
Use this setting when the terminal is not used or when using the terminal as a throughput.
When set to "F", the output is not set by any drive function but it can be switched by a PLC via a communication option or
MEMOBUS/Modbus communications (through mode).
Setting 10: Minor Fault
Output closes when a minor fault condition is present.
Setting 11: Reset Command Active
Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.
Setting 12: Timer Output
This setting configures a digital output terminal as output for the timer function.
details.
Setting 13: Speed Agree 2 (f
Closes whenever the actual output frequency is within the Speed Agree Width (L4-04) of the current frequency reference
regardless of the direction.
Status
Open
Output frequency does not match the frequency reference while the drive is running
Closed
Output frequency is within the range of frequency reference ± L4-04
Note:
The detection works in both forward and reverse.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Torque Detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque Detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque Detection 2 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
Torque Detection 2 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
for details.
/f
Agree 2)
ref
out
Description
Refer to L4-05: Frequency Reference
Refer to b4: Delay Timers on page 135
Description