YASKAWA CIMR-VU BA0001 Technical Manual page 148

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

5.3 C: Tuning
Switching Accel/decel Times by a Frequency Level
The drive can automatically switch from accel/decel times 4 (C1-07 and C1-08) to the default accel/decel times (C1-01/02 for
motor 1, C1-05/06 for motor 2) when the output frequency exceeds the frequency level set in parameter C1-11. When it falls
below this level, the accel/decel times are switched back.
Note:
Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by a frequency level. For example,
if accel/decel time 2 is selected, the drive will use this time only and not switch from accel/decel time 4 to the selected one.
(accel time from 0 Hz to C1-11)
C1-03 =
(accel time between C1-11 and E1-04)
C1-01 =
(decel time between E1-04 and C1-11)
C1-02 =
(decel time from C1-11 to 0 Hz)
C1-04 =
Switching Acceleration and Deceleration Times by Motor Selection
When switching between motor 1 and 2 using a digital input (H1-oo = 16) parameters C1-01 to C1-04 become accel/decel
time 1/2 for motor 1 and C1-05 to C1-08 become accel/decel time 1/2 for motor 2. In this case the digital input "Accel/Decel
Time 2 Selection" cannot be used (this would trigger an oPE03 error, indicating a contradictory multi-function input settings).
Table 5.10
explains the activation of accel/decel times depending on the motor selection and accel/decel time selection.
Accel/Decel Time 1 (H1-oo = 7)
Open
Closed
n
C1-09: Fast-stop Time
Parameter C1-09 will set a special deceleration that is used when certain faults occur or that can be operated by closing a
digital input configured as H1-oo = 15 (N.O. input) or H1-oo = 17 (N.C. input). The input does not have to be closed
continuously, even a momentary closure will trigger the Fast-stop operation.
Unlike standard deceleration, once the Fast-stop operation is initiated, the drive cannot be restarted until the deceleration is
complete, the Fast-stop input is cleared, and the Run command is cycled.
A digital output programmed for "During Fast-stop" (H2-01/02/03 = 4C) will be closed as long as Fast-stop is active.
No.
C1-09
<1> The setting range for the acceleration and deceleration times is determined by C1-10 (Accel/Decel Time Setting Units). For example, if the time is
set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this
uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast-stop time to C1-09.
n
C1-10: Accel/Decel Time Setting Units
Determines the units for the acceleration and deceleration times set to C1-01 through C1-09 using parameter C1-10.
No.
C1-10
Setting 0: 0.01 s Units
The accel/decel. times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. If any of the parameters C1-01 to
C1-09 is set to 600.1 seconds or more, then C1-10 cannot be set to 0.
Setting 1: 0.1 s Units
The accel/decel. times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.
148
×
(E1-04)
C1-11
×
(E1-04)
(E1-04 - C1-11)
×
(E1-04)
(E1-04 - C1-11)
×
(E1-04)
C1-11
Figure 5.23 Accel/Decel Time Switching Frequency
Table 5.10 Motor Switching and Accel/Decel Time Combinations
Motor 1 Selected
Accel
C1-01
C1-03
Parameter Name
Fast-stop Time
Parameter Name
Accel/Decel Time Setting Units
Figure 5.23
shows an operation example.
Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
C1-03
C1-01
setting
setting
When the output frequency
C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-03, -04)
Decel
C1-02
C1-04
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
C1-02
C1-04
setting
setting
Motor 2 Selected
Accel
C1-05
C1-07
Setting Range
<1>
0.0 to 6000.0 s
Setting Range
0 or 1
Decel
C1-06
C1-08
Default
10.0 s
Default
1