B.2 Parameter Table
H2-oo
Function
Setting
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
Reverse Direction
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1E
Restart Enabled
1F
Overload Alarm oL1
20
oH Pre alarm
Mechanical Weakening
22
(N.O.)
2F
Maintenance Period
<1>
30
During Torque Limit
37
During Frequency Output
38
Drive Enable
39
Watt Hour Pulse Output
3C
LOCAL/REMOTE Status
3D
Speed Search
3E
PID Feedback Loss Low
3F
PID Feedback Loss High
4A
KEB Operation
4B
Short-Circuit Brake
4C
During Fast-stop
4D
oH Pre-alarm Time Limit
4E
Braking Transistor Fault (rr)
<1>
4F
Braking Resistor Overheat
<1>
(oH)
90 to 92
DWEZ Digital Outputs 1 to 3
H2 Parameter Functions
100 to 192
Reversed Output Switching of
0 to 92
<1> Available in drive software versions PRG: 1016 and later.
380
H2 Multi-Function Digital Output Settings
Open: When the output current/torque exceeds the value set in parameter L6-02 for more
time than is set in parameter L6-03.
Closed: When the output current/torque exceeds the value set in parameter L6-05 for
more time than is set in parameter L6-06.
Open: Output current/torque exceeds the value set in parameter L6-05 for more time
than is set in parameter L6-06.
Closed: Drive is running in the reverse direction.
Open: Drive is in Baseblock condition. Output is disabled.
Closed: Motor 2 is selected by a digital input (H1-oo = 16)
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater.
Closed: Heatsink temperature exceeds the parameter L8-02 value.
Closed: Mechanical Weakening detected.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may
require maintenance.
Closed: When the torque limit has been reached.
Open: No frequency output from drive if stopped, with baseblock, with DC injection
braking during initial excitation, or with short-circuit braking.
Closed: Drive is outputting a frequency
Closed: Multi-function input closes (H1-oo = 6A)
Output units are determined by H2-06, outputs 200 ms pulse for each incremented kWh
count.
Closed: LOCAL
Open: REMOTE
Closed: Speed search is being executed.
Closed: PID Feedback Loss Low.
PID feedback value is below the level set to b5-13 for longer than the time set in b5-14.
Closed: PID Feedback Loss High.
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37.
Closed: KEB is being performed.
Closed: Short-Circuit Braking is active.
Closed: Fast-stop command is entered
Closed: oH Pre-alarm time limit is passed.
Closed: The built-in dynamic braking transistor failed.
Closed: The dynamic braking resistor has overheated.
Reserved for DWEZ digital output functions.
Reverse the output switching of the multi-function output functions. Set the last two
digits of 1oo to reverse the output signal of that specific function.
Examples:
Setting "108" reverses the output of "During baseblock," which is setting value 08.
Setting "14A" reverses the output of "During KEB operation", which is setting "4A".
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Description
Control
Mode
Pg.
O
V/
P
L
f
M
V
O O O
198
O O O
198
O O O
198
O O O
201
O O O
202
O O −
202
O O O
202
O O O
202
O O O
202
O O O
202
O O O
202
− O −
202
O O O
202
O O O
203
O O O
203
O O O
203
O O O
203
O O O
203
O O O
203
O O O
203
− O
203
O O O
203
O O O
203
O O O
203
O O O
203
O O O
204
O O O
204

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents