YASKAWA CIMR-VU BA0001 Technical Manual page 117

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

• For use when the motor parameters are unknown and Auto-tuning can not be performed.
Setting 2: Open Loop Vector
• For general, variable-speed applications.
• For applications requiring precise speed control, quick response, and higher torque at low speeds.
Setting 5: PM Open Loop Vector
For operating SPM, IPM, and various permanent magnet motors. Takes advantage of Energy Saving features when operating
with derated torque.
n
A1-03: Initialize Parameters
Resets parameter settings back to their original default values. After the initialization the parameter automatically returns to
0.
No.
A1-03
Setting 0: No Initialization
Setting 1110: User Initialize
The modified drive parameters are returned to the values selected as user settings. User settings are stored when parameter
o2-03 = "1: Set Defaults".
Note:
A "user-initialization" resets all parameters to a user-defined set of default values that were previously saved to the drive. To clear the user-
defined default values, set parameter o2-03 to "2".
Setting 2220: 2-Wire Initialization
Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as forward run and reverse
run, respectively. A 2-wire sequence assigns functions to input terminals S1 and S2.
Refer to Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence on page 191
Setting 3330: 3-Wire Initialization
The drive parameters are returned to factory default values with digital inputs S1, S2, and S5 configured as run, stop, and
forward/reverse respectively. A 3-wire sequence assigns functions to input terminals S1, S2, and S5.
Refer to Setting 0: 3-Wire Sequence on page 185
Setting 5550: oPE04 Reset
If parameters on a certain drive have been edited and then a different terminal block is installed with different settings saved
in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the terminal block
memory, set A1-03 to "5550".
Notes on Parameter Initialization
The parameters shown in
Table 5.1
history will not be reset when the drive is initialized by A1-03 = 2220 or 3330. Although the control mode in A1-02 is not
reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
No.
A1-00
A1-02
A1-07
E1-03
E5-01
E5-02
E5-03
E5-04
E5-05
E5-06
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Parameter Name
Initialize Parameters
for more information.
will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. The fault
Table 5.1 Parameters not Changed by Drive Initialization
Setting Range
0, 1110, 2220, 3330, 5550
Parameter Name
Language Selection
Control Method Selection
DriveWorksEZ Function Selection
V/f Pattern Selection
Motor Code Selection (for PM motors)
Motor Rated Capacity (for PM motors)
Motor Rated Current (for PM motors)
Motor Poles (for PM motors)
Motor Stator Resistance (for PM motors)
Motor d Axis Inductance (for PM motors)
5.1 A: Initialization
Default
0
for more information.
117
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents