Digital Operator Display
H3-02 and H3-10 are set to the same value.
The following simultaneous contradictory
settings: H3-02 or H3-10 = B (PID Feedback)
H6-01 (Pulse Train Input) = 1 (PID Feedback)
The following simultaneous contradictory
settings: H3-02 or H3-10 = C (PID Target
Value) H6-01 = 2 (pulse train input sets the
PID target value)
The following simultaneous contradictory
settings: H3-02 or H3-10 = C (PID Target
Value) b5-18 = 1 (enables b5-19 as the target
PID value)
The following simultaneous contradictory
settings: H6-01 or H3-10 = C (PID Target
Value) b5-18 = 1 (enables b5-19 as the target
PID value)
Digital Operator Display
Cause
Attempted to use a function in the V/f motor
control method that is only possible in Open
Loop Vector Control.
Simple V/f with PG was enabled while not in
V/f Control (H6-01 = 3).
In Open Loop Vector Control, n2-02 is greater
than n2-03
In Open Loop Vector Control, C4-02 is greater
than C4-06
In OLV/PMl, parameters E5-02 to E5-07 are
set to 0.
The following conditions are true in PM Open
Loop Vector Control:
• E5-03 does not equal 0
• E5-09 and E5-24 are both equal to 0, or
neither equals 0
Note: Use U1-18 to find parameters set outside of the specified setting range. Other errors are given precedence over oPE08 when multiple errors occur
simultaneously.
Digital Operator Display
Cause
The following simultaneous contradictory
settings:
• b5-15 not 0.0 (PID Sleep Function
Operation Level)
• The stopping method is set to either DC
injection braking or coast to stop with a
timer (b1-03 = 2 or 3).
• D control is being used on the setpoint
deviation (b5-01 = 1) or on the feedback
value (b5-01 = 2).
• A negative PID output value is set to operate
the drive in reverse (b5-11 = 1) and the
frequency reference lower limit greater than
0 (d2-02 > 0).
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Change the settings to H3-02 and H3-10 so that functions no longer conflict.
Note: Both 0 (primary analog frequency reference) and F (Not Used) can be set to H3-02 and H3-10 at
the same time.
Disable one of the PID selections.
Parameter Selection Error
oPE08
A function has been set that cannot be used in the motor control method selected.
Check the motor control method and the functions available.
To use Simple V/f with PG, ensure the motor control method has been set to V/f Control (A1-02 = 0).
Correct parameter settings so that n2-02 is less than n2-03.
Correct parameter settings so that C4-02 is less than C4-06.
• Set the correct motor code in accordance with the motor being used (E5-01).
• When using a special-purpose motor, set E5-oo in accordance with the Test Report provided.
• Set E5-09 or E5-24 to the correct value, and set the other to "0".
• Set the motor-rated current for PM to "0" (E5-03).
PID Control Selection Fault
oPE09
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4).
• Set b5-15 to a value other than 0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
Set parameters b5-01, b5-11, and d2-02 to the proper values.
6.6 Operator Programming Errors
Fault Name
Fault Name
Possible Solution
Fault Name
Possible Solution
6