YASKAWA CIMR-VU BA0001 Technical Manual page 107

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

PRG: 1015 and earlier: 0.00 to 650.00 kW
n
T1-03: Motor Rated Voltage (T1-01 = 0 or 3)
Used to set the motor rated voltage according to the motor nameplate value. If the motor is used above its base speed, enter
the voltage at base speed here.
For higher tuning precision and better control performance, enter the motor no-load voltage here if known. The motor no-load
voltage is referred as to the voltage needed to operate the motor under no-load condition at its rated speed. Refer to the motor
data sheet.
No.
T1-03
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.
n
T1-04: Motor Rated Current
Used to set the motor rated current according to the motor nameplate value. For optimal performance in OLV, the motor rated
current should be between 50 and 100% of the drive rating. Enter the current at the motor base speed.
No.
T1-04
n
T1-05: Motor Rated Frequency (T1-01 = 0 or 3)
Used to set the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used
or the motor is used in the field weakening area, enter the base frequency here.
For higher tuning precision and better control performance, enter the motor no-load frequency here if known. The "no-load
frequency" refers to the frequency needed to operate the motor under no-load condition at its rated speed. Refer to the motor
data sheet.
No.
T1-05
n
T1-06: Number of Motor Poles (T1-01 = 0 or 3)
Used to set the number of motor poles according to the motor nameplate value.
No.
T1-06
n
T1-07: Motor Base Speed (T1-01 = 0 or 3)
Used to set the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used or
the motor is used in the field weakening area, enter the speed at base frequency here.
No.
T1-07
n
T1-11: Motor Iron Loss (T1-01 = 3)
Provides iron loss information for determining the Energy Saving coefficient. If E2-10 has been changed and the power has
been cycled, the value set to E2-10 will appear as the default in T1-11. If the value of T1-02 is not changed during Auto-
Tuning data input, the drive will select a value that is typical for the motor power entered to T1-02.
No.
T1-11
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Name
Motor Rated Voltage
Name
Motor Rated Current
Name
Motor Base Frequency
Name
Number of Motor Poles
Name
Motor Base Speed
Name
Motor Iron Loss
4.7 Auto-Tuning
Setting Range
<1>
0.0 to 255.5 V
Setting Range
10 to 200% of drive rated
current
Setting Range
0.0 to 400.0 Hz
Setting Range
2 to 48
Setting Range
0 to 24000 r/min
Setting Range
0 to 65535 W
Default
<1>
200.0 V
Default
Determined by
o2-04 and C6-01
Default
60.0 Hz
Default
4
4
Default
1750 r/min
Default
Determined by
o2-04 and C6-01
107