Setting 38: Drive Enabled
A Drive Enable digital output will reflect the status of a digital input configured as a Drive Enable input (H1-oo = 6A). If
the Drive Enable digital input is closed then the Drive Enabled digital output will also close.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours.
Setting 3C: LOCAL/REMOTE Status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
Open
REMOTE: The selected external reference (b1-01/b1-02 or b1-15/b1-16) is used as frequency reference and Run command source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Speed Search function.
Setting 3E: PID Feedback Low
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the level
set to b5-13 for longer than the time set to b5-14.
Setting 3F: PID Feedback High
Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the level
set to b5-36 for longer than the time set to b5-37.
Setting 4A: During KEB Operation
Output terminal closes while KEB is being performed.
KEB function description.
Setting 4B: During Short Circuit Braking
Closes the output terminal while Short Circuit Braking is being executed.
Setting 4C: During Fast-stop
Output terminal closes when a Fast-stop is being executed.
Setting 4D: oH Pre-Alarm Time Limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat alarm
has not disappeared after ten frequency reduction operation cycles.
Selection on page 235
for details.
Setting 4E: Braking Transistor Fault (rr)
The output closes when the internal braking transistor reaches the overheat level.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
OFF
ON
run command
baseblock
OFF
command
output
frequency
OFF
ON
during run
OFF
during frequency
output
Figure 5.66 During Frequency Output Time Chart
Refer to H2-06: Watt Hour Output Unit Selection on page 204
Refer to PID Feedback Loss Detection on page 141
Refer to PID Feedback Loss Detection on page 141
ON
ON
Description
Refer to b3: Speed Search on page 130
Refer to Kinetic Energy Backup (KEB) Function on page 219
C1-09: Fast-stop Time
Refer to L8-03: Overheat Pre-Alarm Operation
5.7 H: Terminal Functions
for details.
for details on the
for details.
for details.
for details.
5
for a
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents