YASKAWA CIMR-VU BA0001 Technical Manual page 390

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

B.2 Parameter Table
No.
Name
Overheat Pre-Alarm
L8-03
Operation Selection
Input Phase Loss Protection
L8-05
Selection
Output Phase Loss Protection
L8-07
Selection
Output Ground Fault
L8-09
Detection Selection
Heatsink Cooling Fan
L8-10
Operation Selection
Heatsink Cooling Fan
L8-11
Operation Delay Time
Ambient Temperature Setting Used to input the ambient temperature. This value adjusts the
L8-12
oL2 Characteristics Selection
L8-15
at Low Speeds
L8-18
Soft Current Limit Selection
Frequency Reduction Rate
L8-19
during oH Pre-Alarm
Current Unbalance Detection
L8-29
(LF2)
L8-35
Installation Method Selection
Carrier Frequency
L8-38
Reduction
390
Description
Sets the drive operation when an overheat alarm oH is
detected.
0: Ramp to Stop using the active decel time.
1: Coast to Stop.
2: Fast-stop using the time set in C1-09.
3: Alarm Only. Drive continues running, but displays an alarm.
4: Reduced Speed Operation. Drive continues to run with
reduced frequency reference as specified in L8-19.
Settings 0 through 2 trigger a fault relay if the heatsink
becomes too hot.
Selects the detection of input current phase loss, power supply
voltage imbalance, or main circuit electrolytic capacitor
deterioration.
0: Disabled
1: Enabled
Note: This parameter is disabled in 200 V single-phase drives.
Selects the output phase loss detection.
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
Output phase loss is detected when operating with less than
5% of the drive rated current. Detection can mistakenly occur
if the motor is small relative to the drive capacity rating (this
parameter should be disabled in such cases).
Selects the output ground fault detection.
0: Disabled
1: Enabled
Controls the heatsink cooling fan operation.
0: Run with timer (Fan operates only during run and for L8-11
seconds after stop.)
1: Run always (Cooling fan operates whenever the drive is
powered up.)
This parameter sets the delay time for the cooling fan to shut
off after the run command is removed when L8-10 = 0.
drives oL2 detection level.
Sets the oL2 characteristics at output frequencies below 6 Hz.
0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0
Hz.
Selects the software current limit function. Typically no
adjustment is required.
0: Disabled
1: Enabled
Specifies the frequency reference reduction gain at overheat
pre-alarm when L8-03 = 4.
Selects the detection of unbalanced output currents caused by
faulty devices in the output circuit.
0: Disabled
1: Enabled
Selects the installation type:
0: IP20/Open-Chassis Drive, IP00/Open-Chassis Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
Provides protection to the IGBTs by reducing the carrier
frequency at low speeds.
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the whole speed range
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Control
Mode
Range
Def.
O
V/
P
L
f
M
V
0 to 4
3
A A A
0, 1
1
A A A
0 to 2
1
A A A
<3>
0, 1
A A A
0, 1
0
A A A
0 to 300
60 s
A A A
-10 to 50 40 °C A A A
0, 1
1
A A A
<15>
0, 1
A A −
0.1 to 1.0
0.8
A A A
0, 1
1
− A
2
0 to 3
Α Α A
<13>
<3>
0 to 2
A A A
Addr.
Pg.
Hex
4AF
235
4B1
236
4B3
236
4B5
237
4B6
237
4B7
237
4B8
237
4BB
237
4BE
238
4BF
236
4DF
238
4EC
238
4EF
238