D.3 UL and CSA Standards
n
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred.
Branch circuit protection shall be provided by any of the following according to
• Non-time Delay Class J, T, or CC fuses.
• Time Delay Class J, T, CC, or RK5 fuses.
• Semiconductor fuses.
• Molded Case Circuit Breakers (MCCB).
Non-time Delay
Drive Model
Fuse Rating (A)
<1>
BA0001
6
BA0002
10
BA0003
20
BA0006
40
BA0010
40
BA0012
50
BA0018
80
2A0001
3
<6>
2A0002
6
<7>
2A0004
15
2A0006
20
2A0010
25
2A0012
25
2A0020
40
2A0030
2A0040
2A0056
2A0069
4A0001
3
4A0002
6
<7>
4A0004
15
<8>
4A0005
20
<9>
4A0007
25
4A0009
25
4A0011
30
4A0018
4A0023
4A0031
4A0038
<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004, 4A0004, 4A0005, and 4A0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.
<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
478
Table D.10 Factory Recommended Drive Branch Circuit Protection
Time Delay Fuses
Class J, T, or CC
Class RK5
Fuse Rating (A)
Fuse Rating (A)
<2>
200 V Class Single-Phase Drives
3.5
6
10
20
35
40
60
200 V Class Three-Phase Drives
1.5
3
6
10
15
20
40
60
90
110
125
400 V Class Three-Phase Drives
2
3.5
7
10
12
15
20
35
40
60
70
Bussmann
Semiconductor
Fuse Part Number
(Fuse Ampere)
<3>
4
FWH-25A14F (25)
8
FWH-25A14F (25)
15
FWH-60B (60)
30
FWH-80B (80)
45
FWH-100B (100)
50
FWH-125B (125)
70
FWH-175B (175)
2
FWH-25A14F (25)
3
FWH-25A14F (25)
8
FWH-25A14F (25)
15
FWH-25A14F (25)
20
FWH-70B (70)
30
FWH-70B (70)
50
FWH-90B (90)
80
FWH-100B (100)
110
FWH-200B (200)
150
FWH-200B (200)
175
FWH-200B (200)
2
FWH-40B (40)
3
FWH-40B (40)
8
FWH-50B (50)
10
FWH-70B (70)
15
FWH-70B (70)
20
FWH-90B (90)
30
FWH-90B (90)
45
FWH-80B (80)
50
FWH-100B (100)
80
FWH-125B (125)
90
FWH-200B (200)
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Table
D.10.
MCCB
Rating (A)
<4>
15
15
15
30
50
60
80
15
15
15
15
25
30
60
90
125
150
200
15
15
15
15
20
20
35
50
60
90
110
<5>
Minimum
Enclosure
3
Volume (in
)
600
600
600
1152
1152
1152
1152
600
600
600
1152
1152
1152
1152
1152
1152
2560
2560
1152
1152
1152
1152
1152
1152
1152
1152
1152
1152
1152

Hide quick links: