YASKAWA CIMR-VU BA0001 Technical Manual page 73

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

L8-01: Internal Dynamic Braking Resistor Protection Selection
L3-04: Stall Prevention During Deceleration
Note:
Select either 0 or 3
8.
Operate the system and verify the required deceleration rate is obtained during dynamic braking or stopping.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Table 3.16 Braking Resistor Settings
Parameter
Settings
0: Disabled. The drive will not provide overheat protection.
Supply separate means of overheat protection.
1: Enabled. Braking Resistor is protected from overheat.
0: Stall prevention disabled.
3: Stall prevention enabled with a braking resistor
Note:
This setting cannot be used in OLV control for PM
motor.
3.11 Braking Resistor
73
3