YASKAWA CIMR-VU BA0001 Technical Manual page 379

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

No.
Name
H2-06
Watt Hour Output Unit Selection
<1> The availability of certain functions depends on the control method used.
H2-oo
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency reference selection
A
Run command selection
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
D
Braking Resistor Fault
E
Fault
F
Not used/Through Mode
10
Minor Fault
11
Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Description
Sets the output units for the watt hours when
Watt Hour Pulse Output is selected as the digital
output (H2-01, H2-02, or H2-03 = 39).
Outputs a 200 ms pulse signal when the watt-
hour counter increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output.
Closed: Output frequency is 0.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set
to L4-02).
Closed: Output frequency and speed reference equal the value in L4-01 (plus or minus
the hysteresis of L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01, with hysteresis
determined by L4-02.
Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive
mode.
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: There is no output voltage
Open: External Reference 1 or 2 supplies the frequency reference
Closed: Digital operator supplies the frequency reference.
Open: External Reference 1 or 2 supplies the Run command
Closed: Digital operator supplies the Run command.
Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer
than the time set in parameter L6-03.
Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1.
Closed: Braking resistor or transistor is overheated or faulted out. This selection requires
that braking resistor protection parameter be set for ERF (L8-01 = "1").
Closed: Fault occurred (other than CPF00 and CPF01).
Set this value when the terminal is not used, or when using the terminal in the pass-
through mode.
Closed: An alarm is triggered.
Closed: The drive has received a reset command from the multi-function input terminals
or from serial network, or the digital operator RESET key has been pressed.
Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital input
(H1-oo = 18 "timer function").
Closed: When drive output frequency equals the frequency reference +/- L4-04.
Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus
L4-04).
Closed: When the drive output frequency is less than or equal to the value in L4-03 with
the hysteresis determined by L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03 with
the hysteresis determined by L4-04.
Range
0 to 4
Description
B.2 Parameter Table
Control
Mode
Addr.
Def.
Pg.
O
Hex
V/
P
L
f
M
V
0
A A A
437
204
Control
Mode
Pg.
O
V/
P
L
f
M
V
O O O
195
O O O
196
O O O
196
O O O
196
O O O
197
O O O
197
O O O
198
O O O
198
O O O
198
O O O
198
O O O
198
O O O
198
O O O
199
O O O
199
O O O
199
O O O
199
O O O
199
O O O
199
O O O
199
O O O
199
O O O
200
O O O
200
O O O
201
379