YASKAWA CIMR-VU BA0001 Technical Manual page 191

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

Terminal Status
Setting
N.O.
N.C.
2C
O
2D
2E
O
2F
<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.
Setting 30: PID Integral Reset
By configuring one of the digital inputs as an Integral Reset Input, (H1-oo = 30), the value of the integral component of PID
control can be reset to 0 whenever the configured input is closed. The integral component of PID control will be held at 0 as
long as the configured digital input is held closed.
Setting 31: PID Integral Hold
By configuring a digital input for Integral Hold (H1-0o = 31), the value of the integral component of the PID control is locked
as long as the input is active. The PID controller resumes integral operation from the hold value as soon as the integral hold
input is released.
Refer to PID Block Diagram on page 138
Setting 32: Multi-Step Speed 4
Used to select the Multi-Step Speeds d1-09 to d1-16 in combination with the Multi-Step Speed inputs 1, 2 and 3.
d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160
Setting 34: PID SFS Cancel
A digital input configured as a PID SFS Cancel input (H1-0o = 34) can be used to enable or disable the PID soft starter and
thereby canceling the Accel/Decel time b5-17.
Function 35: PID Input Level Selection
An input programmed for this function can be used to switch the sign of the PID input.
138
for more information on this function.
Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence
Sets the drive for 2-Wire sequence.
When the input set to 40 is closed, the drive operates in the forward direction. When the input set for 41 is closed, the drive
will operate in reverse. Closing both inputs at the same time will result in an external fault.
Note:
1. This function cannot be used simultaneously with settings 42 and 43.
2. These functions are assigned to the terminals S1 and S2 when the drive is initialized for 2-Wire sequence.
3. Software versions PRG: 1013 and later require that both Forward run and Reverse Run commands be set at the same time.
Setting 42/43: Run and Direction Command for 2-Wire Sequence 2
Sets the drive for 2-Wire sequence 2.
When the input programmed for 42 is closed, the drive will operate in the selected direction. When the input opens, the drive
will stop. The input programmed for 43 selects the direction. If it is open, forward direction is selected; if it is closed, reverse
direction is selected.
Note:
This function cannot be used simultaneously with settings 40 and 41.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
<1>
Detection Method
Detected
Always
during Run
Detected
only
O
O
O
O
Refer to PID Block Diagram on page 138
Refer to PID Block Diagram on page 138
Forward Run
Reverse Run
Figure 5.53 Example Wiring Diagram for 2-Wire Sequence
<2>
Ramp to Stop
Coast to Stop
(fault)
O
O
for details.
for details.
Drive
S1
S2
SC
Digital Input Common
5.7 H: Terminal Functions
Stopping Method
Fast-stop
(fault)
(fault)
for details.
for details.
Refer to PID Block Diagram on page
Alarm Only
(continue
running)
O
O
O
O
Refer to
5
191

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents