5.7 H: Terminal Functions
Speed Agree 2
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227
detection width.
Setting 14: User Set Speed Agree 2 (f
Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-04) of the
programmed Speed Agree Level (L4-03). As the detection level L4-03 is a signed value, detection works in the specified
direction only.
Status
Open
Output frequency or frequency reference are outside the range of L4-03 ± L4-04
Closed
Output frequency and the frequency reference are both within the range of L4-03 ± L4-04
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227
detection width.
Setting 15: Frequency Detection 3
Output is closed as long as the output frequency is below the detection level set in L4-03 plus the hysteresis set in L4-04. It
closes when the output frequency falls below L4-03. As the detection level L4-03 is a signed value, the detection works in the
specified direction only.
Status
Open
Output frequency exceeded L4-03 plus L4-04.
Closed
Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
200
Frequency
reference
Output
frequency
OFF
ON
Figure 5.61 Speed Agree 2 Time Chart
/f
Agree 2)
ref
set
Output
frequency
Frequency
reference
User Set
ON
OFF
Speed Agree 2
Figure 5.62 User Set Speed Agree 2 Example with Positive L3-04 Value
L4-04
Description
L4-03
+/- L4-04
Frequency
reference
Description
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
L4-04
for details on setting the
Output
frequency
for details on setting the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents