YASKAWA CIMR-VU BA0001 Technical Manual page 450

Ac drive-v1000 200 v class, three-phase input: 0.1 to 18.5 kw; 200 v class, single-phase input: 0.1 to 3.7 kw; 400 v class, three-phase input: 0.2 to 18.5 kw
Table of Contents

Advertisement

C.10 MEMOBUS/Modbus Data Table
Register No.
Fault Contents 2
bit 0
bit 1
bit 2
0029H
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
Alarm Contents1
bit 0 to bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
002AH
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Input Terminal Status
bit 0
bit 1
bit 2
002BH
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
450
Contents
IGBT Short Circuit or Ground Fault (SC)
Ground Fault (GF)
Input Phase Loss (PF)
Output Phase Loss (LF)
Braking Resistor Overheat (rH)
Reserved
Motor Overheat 2 (PTC input) (oH4)
Reserved
Reserved
Run Command Input Error (EF)
Drive Baseblock (bb)
Overtorque Detection 1 (oL3)
Heatsink Overheat (oH)
Overvoltage (ov)
Undervoltage (Uv)
Reserved
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Undertorque Detection 1/2 (UL3/UL4)
Motor Overheat (oH3)
PID Feedback Loss (FbL, FbH)
Reserved
Serial Communication Transmission Error (CALL)
Terminal S1 Closed
Terminal S2 Closed
Terminal S3 Closed
Terminal S4 Closed
Terminal S5 Closed
Terminal S6 Closed
Terminal S7 Closed
Reserved
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents