Alarm Codes For The Kpi (E/H/X)3E Series And Dx Interface - Hitachi RAS-2-HVNP Service Manual

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

8. Troubleshooting
8.2.4  Alarm codes for the KPI (E/H/X)3E Series and DX Interface
Code
DX-
KPI-
KPI-
No.
KIT2
S3
Active
01
o
-
o
03
o
-
o
11
o
o
o
12
o
o
o
13
o
-
o
14
o
-
o
15
-
-
-
16
-
-
o
17
-
-
o
18
(o)
o
o
19
o
o
o
31
o
-
o
35
o
-
o
70
o
o
o
71
o
o
o
EE
o
-
o
74
-
-
-
252
SMGB0079 rev.0 - 01/2013
Category
Type of Abnormality
Indoor
Activation of protection device
Transmission
Transmission Error
Indoor
Air inlet thermistor (RA for KPI)
Indoor
Air outlet thermistor (OA for KPI)
Indoor
Liquid pipe thermistor
Indoor
Gas pipe thermistor
Fresh Outdoor Air Thermistor
Indoor
(Econofresh)
Indoor
Air inlet DX Coil thermistor (Tincoil)
Air outlet DX Coil thermistor (Tout-
Indoor
coil)
Indoor RA fan protection device
Indoor
activation for KP
Indoor OA fan protection device
Indoor
activation for KPI or DX-KIT2 Fan
Incorrect setting of outdoor and
System
indoor units
System
Indoor Unit Number Setting Error
Abnormal transmission between
Indoor
PCB1 and PCB2
Indoor
Incorrect PCBs setting
Compressor protection alarm (can-
Compressor
not be reset from the remote con-
troller)
Indoor
Remote sensor thermistor (Trem)
Main cause
Float switch activation (high water level in drain hose or
abnormality in drain pipe, float switch or drain pan).
Outdoor fuse meltdown, Indoor/outdoor connection wir-
ing (breaking, wiring error, etc.)
Loose, disconnected, broken or short-circuited connector
Loose, disconnected, broken or short-circuited connector
Loose, disconnected, broken or short-circuited connector
Loose, disconnected, broken or short-circuited connector
Loose, disconnected, broken or short-circuited connector
Loose, disconnected, broken or short-circuited connector
Loose, disconnected, broken or short-circuited connector
Fan motor overheating, locking.
Fan motor overheating, locking.,
Outdoor/Indoor Unit capacity setting error, Indoor total ca-
pacity excessively large/small
Indoor units with the same number exist in a refrigerant
piping system
Loose, disconnected
Wrong setting are performed in PCBs
This alarm code is displayed when the following alarms
are triggered three times within six hours: 02,07,08,39,43
to 45, 47
Loose, disconnected, broken or short-circuited con-
nector