Checking Procedure For Other Parts - Hitachi RAS-2-HVNP Service Manual

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

8. Troubleshooting
8.4.6  Checking procedure for other parts
Part name
Solenoid Valve Coil
Reversing Valve Coil
Compressor
Magnet Contactor
286
SMGB0079 rev.0 - 01/2013
Model code
SR10D
VHV-01AP552B1
STF-G01AG579A1
EU1014D9
EU140XA2
EU180XA1
2YC45HXD
2YC63FXD
E402HHD-36A2
E401HHD-36A2
E507DHD-50A2
E657DHD-65A2
E655DHD-65D2
FC-1/SP
FC-0/SP
Resistance (Ω)
Unit models
1250
RAS-(3-12)H(V)NP(E)
RAS-(4-12)H(V)NC(E)
(at 20
C)
o
1473
RAS-(3-12)H(V)NP(E)
(at 20
C)
o
950
RAS-(2-2.5)HVNP
RAS-(3-12)H(V)NC(E)
(at 75
C)
o
1.138
RAS-2HVNP
(at 75
C)
o
1.138
RAS-2.5HVNP
(at 75
C)
o
1.138
RAS-3HVNC
(at 75
C)
o
0.644
RAS-3HVNPE
at 75 ºC
0.310
RAS-4H(V)NCE
(at 75
C)
o
0.460
RAS-(4-6)H(V)NPE
(at 75 ºC)
0.282
RAS-(5-6)H(V)NCE
(at 75 ºC)
0.136
RAS-8HNPE
(at 75 ºC)
0.094
RAS-(10-12)HNP(E)
(at 75 ºC)
0.199
RAS-(8-12)HNC(E)
(at 75 ºC)
460
RAS-(8-12)HN(P/C)(E)
(at 20
C)
o
1150
RAS-(3-6)H(V)NPE
(at 20
C)
o