10. Servicing

 
Removing Inverter module
1  Remove the service cover following
2  Open the P plate turning counter clockwise approximately 90° following
Check that the LED201 (red) on Inverter is OFF when the P plate is opened.
D A N G E R
DO NOT touch electrical components while the LED201 (Red) is ON to avoid electrical shock. Wait until the
LED turns off.
3  Remove all the wiring connected on the Inverter.
4  Remove 4 screws which fix the Inverter.
Hold the wires placed at the left side.
5  Pull the Inverter toward right side from the front of the pro-
duct. (Remove along with the plastic case and the radiation
fin).