4. Electrical wiring

 
Main switch protection
Select the main switches in according to the next table:
Model
All Indoor Units
ELB: Earth switch; CB: Circuit braker
IVX Premium series
IVX Standard series
100
SMGB0079 rev.0 - 01/2013
Power supply
1~ 230V 50Hz
Outdoor unit
MC (A)
RAS-2HVNP
12.0
RAS-2.5HVNP
14.0
RAS-3HVNPE
19.0
RAS-4HVNPE
28.0
RAS-5HVNPE
28.0
RAS-6HVNPE
28.0
RAS-4HNPE
11.5
RAS-5HNPE
11.5
RAS-6HNPE
13.5
RAS-8HNPE
24.0
RAS-10HNPE
24.0
RAS-12HNP
24.3
Outdoor unit
MC (A)
RAS-3HVNC
16.0
RAS-4HVNCE
28.0
RAS-5HVNCE
28.0
RAS-6HVNCE
28.0
RAS-4HNCE
15.0
RAS-5HNCE
15.0
RAS-6HNCE
15.0
RAS-8HNCE
24.0
RAS-10HNCE
24.0
RAS-12HNC
24.3
Max. current (A)
CB (A)
5.0
6
CB (A)
ELB
16
20
20
2/40/30
32
32
32
15
15
15
4/40/30
30
30
30
CB (A)
ELB
20
32
2/40/30
32
32
20
20
20
4/40/30
30
30
30
ELB (no.
poles/A/mA)
2/40/30