Hitachi RAS-2-HVNP Service Manual page 78

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

3. Piping work and refrigerant charge
IVX Standard series
Outdoor Unit
Maximum piping length
between the outdoor unit
and the farthest indoor
unit
Total piping length
Maximum piping line
after first branch
Main piping length A
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
Maximum height difference Indoor / Indoor
Maximum height difference:
branch pipe/Indoor (2,3 and 4 indoor units system)
branch pipe/branch pipe (4 indoor units system)
(B-C) / (B-D) / (C-D) / (C+G)-(B+E) / (C+G)-(B+D) /
(C+F)-(B+E) / (C+F)-(B+D)
N O T E
• The liquid piping and the gas piping must be of the same piping length and run along the same route.
• Install the branch piping as much as possible near the indoor units
• Install Multikits at the same horizontal level.
64
Actual Length (L)
Equivalent Length (EL)
2 units (A+B+C)
3 units (A+B+C+D)
4 units
(A+B+C+D+E+F+G+)
2 and 3 units (B, C, D)
4 units
(B+D, B+E, C+F, C+G)
SMGB0079 rev.0 - 01/2013
3HP
4HP
5HP
50
70
75
70
90
95
60
80
85
--
90
95
--
90
95
10
--
10
A > B, C, D, E, F, G
6HP
8HP
10HP
100
125
100
115
100
130
100
145
15
15
30 / 20
3
3
< 8
(m)
12HP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents