Hitachi RAS-2-HVNP Service Manual page 284

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

8. Troubleshooting
RAS-(3-12)H(V)NP(E)
Item
Input/output state of outdoor micro-
computer
Capacity of operating indoor unit
Control software No.
Inverter software No.
Inverter order frequency to compressor
Air flow ratio
Outdoor unit expansion valve opening
Discharge pressure (high)
Temperature at the top of compressor
Evaporating temperature at heating
Ambient air temperature
Inverter fin temperature
Inverter firstly current
Inverter secondary current
Outdoor unit address
Indoor unit expansion valve opening
Liquid pipe temperature of indoor unit
(freeze protection)
Indoor unit intake air temperature
Indoor unit discharge air temperature
Cause of indoor unit stoppage
Accumulated Operating Time of Com-
pressor
Accumulated Operating Time of Com-
pressor
Alarm code for abnormal stoppage of
compressor
Cause of stoppage at inverter
Abnormal data record
Total capacity of indoor unit connected
Connected indoor unit number
Refrigerant adress
270
SMGB0079 rev.0 - 01/2013
Item
Check
In-
In-
No.
dic.
dic.
Indicates only for the segments corresponding to the equipment in
01
SC
the figure. (See figure above)
00~199
02
oP 11
In case that capacity is higher than 100, the last two digits flash
Control Software No. in use is indicated. Alternately upper 2 digits
SP 11
03
and lower 2 digits are indicated every 0.5 sec.
Control Software No. in use is indicated. Alternately upper 2 digits
04
iP 11
and lower 2 digits are indicated every 0.5 sec.
0~115 ( Hz)
HI 74
05
In case that frequency is higher than 100Hz, the last two digits flicker
Fo 80
06
00~15
00~100 (%)
07
Eo 30
In case that expansion valve opening is 100%, "
08
Pd 30
0.1 to 4.9 MPa
00~142 (ºC)
09
d 02
In case that temperature is higher than 100ºC, the last two digits flash
10
E 2
-19~80ºC
o -3
11
-19~80ºC
-10~100 (ºC)
F 20
12
In case that temperature is 100%, "
00~199 (A)
A1 12
13
In case that current is higher than 100ºC, the last two digits flash
00~199 (A)
A2 20
14
In case that current is higher than 100ºC, the last two digits flash
15
nA 00
00~63
00~100 (%)
In case that opening is
16
EA 20
100%. "
17
LA 05
-19~127 (ºC)
18
iA 28
-19~127 (ºC)
19
oA 20
-19~127 (ºC)
dA 05
20
(See table at the next page)
0 to 9,999 (x 10 hours)
UJ 00
21
Alternately upper 2 digits and lower 2 digits are indicated every
0.5 sec.
0 to 9,999 (x 10 hours)
cU 00
22
Alternately upper 2 digits and lower 2 digits are indicated every
0.5 sec.
AC 08
23
Alarm code on compressor
i
1
24
(See table at the next page)
One of the abnormal data record from latest (n1) to oldest (n9) is
25
n1 00
indicated. Alarm code or cause code is indicated.
00~199
CP 22
26
In case that capacity is higher than 100, the last two digits flash
AA
2
27
00~64
28
GA
0
00~63
Indication data
Contents
00
In case of twin/triple/quad-type unit,
the information of 2nd to the 4th indo-
or units is indicated repeatedly.
00
" flashes
The right character of the indication
represents the indoor unit setting No.
Single: A
Twin: A, b
Triple: A, b, c
Quad: A, b, c, d
00
" flashes
" flashes