Hitachi RAS-2-HVNP Service Manual page 301

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

8. Troubleshooting

 
Checking procedure for the compressor
CHECK LIST ON COMPRESSOR
Client:
Serie No.
No.
Check item
1
Is THM9 correctly connected?
THM9: Discharge Gas
Thermistor
2
Is thermistor THM9
disconnected?
3
Is current sensor faulty?
4
Is current sensing part on
PCB2 faulty?
5
Is the direction of current
sensor CTU, CTV) reverse?
6
Are power source wires, U
and V inserted correctly into
current sensor? .
7
Is exp. valve (MV1) correctly
connected?
8
Is exp. valve coil (MV1)
correctly connected?
9
Are the refrigeration cycle
and electrical wiring system
incorrectly connected?
10
Is opening of exp. valve
completely closed (locked)?
11
Is opening of exp. valve fully
opened locked)?
12
Are the contacts for comp.
magnetic switch CMC1 faulty?
Is there any voltage
13
abnormality among L1-L2, L2-
L3 and L3-L1?
Is the comp. oil acidified
14
during compressor motor
burning?
287
SMGB0079 rev.0 - 01/2013
Model:
Production Date:
Check method
1. Is wire of thermistor correctly connected by
viewing?
2. Check to ensure the 7-segment indication of
Td when comp. is operating.
Td: Temperature of THM9
1. Check to ensure that thermistor on the top of
comp. is correctly mounted by viewing?
2. Check to ensure that actually measured
temp. is the same as the indication during check
mode.
1. Check to ensure that indication A1 and A2
are 0 during compressor stopping.
2. Check to ensure that indication A1 and A2
are not 0 during compressor running.
Check the direction => by viewing.
Check to ensure that wires are correctly inserted
Check to ensure that MV1 to CN5A is correctly
connected
Check to ensure that each coil is correctly
mounted on the valve.
Check to ensure that refrigerant is flowing into
indoor units by operating one refrigerating cycle
only from the outdoor unit.
Check the following by the check mode of
outdoor units.
1. Liquid Pipe Temp. (TL) < Air Intake Temp.
(Ti) during Cooling Operation
2. Liquid Pipe Temp. (TL) > Air Intake Temp.
(Ti) during Heating Operation
Check to ensure that liquid pipe temp. is lower
than air intake temp. of stopping indoor unit
when other indoor units are operating under
cooling operation.
Check the surface of each contact (L1, L2
and L3) by viewing.
Check to ensure that voltage imbalance is
smaller than 3%.
Please note that power source voltage must be
within 380V or 220V+10%.
Check to ensure that the oil color is not black.
Date:
Checker:
Result
Remarks
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents