2. Unit Installation

 
Wind guard
Specifications
Model
Quantity
Material
Galvanized sheet metal + baked painting
Color
Weight
Fixing screw x 4 [M5 (SUS) x 30]- Unit
Accessories
Fixing Screw x 10 [M5 (SUS) x 12]- Wind Ward
Installation
"Guard net" "Air flow guide" or "Snow protection hood" is
restriction
not available to install with Wind guard
Attaching example of air wind guard
Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 3.1 N.m)
Do not remove the air discharge grille for air flow guide installation.
C A U T I O N
If the air guide is installed without discharge grille it may cause injury due to rotating fan.
Two windguard covers installation
1 Air discharge grille
2 Outdoor unit
3 M5 fixing screw x4 (Accessories)
Service space
Both sides of the outdoor unit should be open.
No obstacles should be placed in the air discharge side.
1 Min.150 mm
2 Outdoor unit
3 Wind guard
31
SMGB0079 rev.0 - 01/2013
WSP-264
1 per unit
UTOPIA Beige
4.0 kg
Installation manual
1
4-6x10 Long Hole
2
5 (Both Sides) - M5 Screw (attachement)
1
2
1
2
1
3
1
2
3
2