Outdoor Units Pcb; Ras-(2-2.5)Hvnp / Ras-3Hvnc - Hitachi RAS-2-HVNP Service Manual

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

5. Control System

5.2 Outdoor units PCB

5.2.1  RAS-(2-2.5)HVNP / RAS-3HVNC
PCB1
PCB1 Connector indication
Connector
PCN5
Crankcase heater of compressor (oil)
PCN6
Reversing valve relay
PCN13
Pressure switch control
PCN401
High pressure switch protection
THM7
Outdoor air temperature thermistor
THM8
Pipe evaporation temperature thermistor
THM9
Compressor discharge temperature thermistor
CN1
Input function
CN2
Demand input
CN5A
Micro electronic expansion valve
CN8
Transmission from outdoor unit to indoor unit
CN17
Transmission to PCB2
CN22
Transmission to IPM
CN24
Motor for outdoor fan
CN25
For inspection
CN26
For inspection
PCB1 Switch indication
Connector
DSW1
No setting
DSW2
Auxiliary function setting
DSW3
Capacity code
DSW4/
Refrigerant cycle number
RSW1
DSW5
Switch
DSW6
Switch
PSW2
Available optional function. Setting can be se-
lected using the 7-segment display
PSW3
PSW351
The inverter micro-computer checking
120
SMGB0079 rev.0 - 01/2013
Name
Name
PCB2
PCB1 LED indication
LED
Colour
LED1
Red
Power source for the PCB
This LED indicates the transmission status
LED2
Green
between the indoor unit and the RCS
This LED indicates the transmission status
LED3
Yellow
between the indoor unit and the outdoor unit
LED351
Red
For inspection
LED353
Red
For inspection
PCB2 Connector indication
Connector
CN21
Transmission to PCB1
CN301
Transmission to PCB1
PCB2 LED indication
LED
Colour
LED1
Red
LED2
Red
These LEDS indicate the cause of unit
stoppages
LED3
Red
LED4
Red
PCB2 Switch indication
Connector
DSW301
Test run
Manual defrost operation switch. The defrost option
PSW1
is manually available under the forced defrost area
Name
Name
Name
Name