Alarm Codes - Hitachi YUTAKI S80 Series Technical Catalogue

Hide thumbs Also See for YUTAKI S80 Series:
Table of Contents

Advertisement

13. Troubleshooting

13.1.2 Alarm codes

LCD dis-
7 segment
Origin
play
display
02
02
Outdoor
Outdoor -
03
03
1st cycle
04
04
Outdoor
05
05
Outdoor
06
06
Outdoor
07
07
Outdoor
08
08
Outdoor
11
11
Hydraulic Water inlet thermistor abnormally (THM
12
12
Hydraulic Water outlet thermistor abnormally (THM
13
13
1st cycle
14
14
1st cycle
15
15
1st cycle
16
16
1st cycle
17
17
1st cycle
18
18
1st cycle
20
20
Outdoor
21
21
1st cycle
22
22
Outdoor
24
24
Outdoor
31
31
Outdoor
35
35
Outdoor
38
38
Outdoor
41
41
Outdoor
42
42
Outdoor
47
47
Outdoor
48
48
Outdoor
51
51
Outdoor
53
53
Outdoor
54
54
Outdoor
55
55
Outdoor
153
TCGB0075 rev.0 - 11/2012
Detail of abnormality
Activation of outdoor unit protection device
(Except for alarm code 42)
Transmission error
Inverter transmission abnormality
Power phase detection abnormality
Undervoltage, overvoltage
Abnormal decrease of discharge gas super-
heat degree
Compressor-Top temperature over-increase
Indoor liquid pipe temperature thermistor
abnormality (THM
)
L
Indoor gas pipe temperature thermistor ab-
normality (THM
)
G
Water outlet C2 thermistor abnormally
(THM
)
WO2
Water DHWT thermistor abnormally (THM
)
HWT
Water swimming pool thermistor abnormally
(THM
)
SWP
Water outlet 3 thermistor abnormally
(THM
)
WO3
Compressor-Top temperature thermistor
abnormality
2nd ambient thermistor abnormally (TH-
M
)
AMB2
Outdoor temperature thermistor abnormality
Outdoor heat exchanger liquid pipe thermis-
tor abnormality
Indoor/Outdoor combination setting error
Indoor unit number setting error
Outdoor protection detection circuit abnor-
mality
Pump down overload
Heating overload
Suction pressure decrease prevention acti-
vated
Overload operation protection activation
Inverter current sensor abnormality
Inverter module error
Inverter fin temperature abnormality
Inverter non-operation
Main factors
High pressure interrupting device activated
Outdoor fuse meltdown, Indoor/outdoor con-
nection wiring (breaking, wiring error, etc.)
Control PCB – Inverter PCB connection wiring
(breaking, wiring error, etc.)
Power source wiring open phase in indoor units
Outdoor PCB abnormality, inverter PCB abnor-
mality, DM, CB abnormality
Excessive refrigerant, expansion valve open-
locked, fan motor locked
Shortage or leakage of refrigerant, piping clog-
ging, fan motor lock
Loose, disconnected, broken or short-circuited
)
connector
WI
Loose, disconnected, broken or short-circuited
)
connector
WO
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
D-
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Loose, disconnected, broken or short-circuited
connector
Outdoor/Indoor unit capacity setting error, indo-
or total capacity excessively large/small
Indoor units with the same number exist in a 
refrigerant piping system
Outdoor PCB abnormality, error in wiring to
outdoor PCB
Outdoor heat exchanger clogging/short circuit, 
broken outdoor fan
Outdoor heat exchanger clogging/short circuit, 
expansion valve close-locked
Shortage or leakage of refrigerant, piping clog-
ging, expansion valve close-locked, fan motor 
locked
Cycle abnormality, Inverter PCB abnormality,
DM abnormality, heat exchanger clogging, etc.
Error in CT wiring, outdoor PCB abnormality,
Inverter PCB abnormality
Compressor, ISPM abnormality, heat exchan-
ger clogging, etc.
Fin thermistor abnormality, heat exchanger 
clogging, fan motor abnormality
Inverter not operating or broken