2. Unit Installation
Wind guard
Specifications
Model
Quantity
Galvanized sheet metal +
Material
Color
Weight
Accessories
Installation
"Guard net" "Air flow guide" or "Snow protection
restriction
hood" is not available to install with Wind guard
Attaching example of air wind guard
•
Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
•
The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 3.1 N.m)
•
Do not remove the air discharge grille for air flow guide installation.
C A U T I O N
If the air guide is installed without discharge grille it may cause injury due to rotating fan.
Two windguard covers installation
1 Air discharge grille
2 Wind guard
3 Outdoor unit
4 M5 fixing screw x4 (Accessories)
Service space
•
Both sides of the outdoor unit should be open.
•
No obstacles should be placed in the air discharge side.
1 Min. 200 mm
2 Outdoor unit
3 Wind guard
41
SMGB0079 rev.0 - 01/2013
WSP-335A
2 per unit
baked painting
Gray (1.0Y8.5/0.5)
5.5 kg
Fixing screw
x 4 [M5 (SUS) x 12]
Installation manual
1
2
2
1
1 Mounting dimension
2 Air flow
3
3
1
2
2
1
1
2
3
2
4